11B-228.3.2.1 Public Use or Common Use EVCS
JUMP TO FULL CODE CHAPTER
Where EVCS are provided for public use or common use, EVCS complying with Section 11B-812 shall be provided in accordance with Table 11B-228.3.2.1. Where new EVCS are installed in facilities with existing EVCS, the "Total Number of EVCS at a Facility" in Table 11B-228.3.2.1 shall include both existing and new EVCS.
Exception: All drive-up EVCS shall comply with Section 11B-812.
ELECTRIC VEHICLE CHARGING STATIONS FOR PUBLIC USE AND COMMON USE
TOTAL NUMBER OF EVCS AT A FACILITY1 | MINIMUM NUMBER (by type) OF EVCS REQUIRED TO COMPLY WITH SECTION 11B-8121 | ||
Van Accessible | Standard Accessible | Ambulatory | |
1 to 4 | 1 | 0 | 0 |
5 to 25 | 1 | 1 | 0 |
26 to 50 | 1 | 1 | 1 |
51 to 75 | 1 | 2 | 2 |
76 to 100 | 1 | 3 | 3 |
101 and over | 1, plus 1 for each 300, or fraction thereof, over 100 | 3, plus 1 for each 60, or fraction thereof, over 100 | 3, plus 1 for each 50, or fraction thereof, over 100 |
- Where an EV charger can simultaneously charge more than one vehicle, the number of EVCS provided shall be considered equivalent to the number of electric vehicles that can be simultaneously charged.
Related Code Sections
11B-228.3.2.1 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Public Use or Common Use EVCS
Where EVCS are provided for public use or common use, EVCS complying with Section 11B -812 shall be provided in accordance with Table 11B-228.3.2.1 ...
Los Angeles Building Code > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-228 Depositories, Vending Machines, Change Machines, Mail Boxes, Fuel Dispensers,and Electric Vehicle Charging Stations > 11B-228.3 Electric Vehicle Charging Stations > 11B-228.3.2 Minimum Number > 11B-228.3.2.1 Public Use or Common Use EVCS
11B-812 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Electric Vehicle Charging Stations
Electric vehicle charging stations (EVCS) shall comply with Section 11B -812 as required by Section 11B -228.3. Where vehicle spaces and access ...
Los Angeles Building Code > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-812 Electric Vehicle Charging Stations
4.106.4.2.1.1 Residential Mandatory Measures, Electric Vehicle Charging Stations (EVCS)
use of the EV charger from the accessible parking space.
The EV space shall be located on an accessible route, as defined in the California Building ...
Los Angeles Green Building Code > 4 Residential Mandatory Measures > 4.106 Site Development > 4.106.4 Electric Vehicle (EV) Charging for New Construction > 4.106.4.2 New Multifamily Dwellings > 4.106.4.2.1 Electric Vehicle Charging Space (EV Space) Locations > 4.106.4.2.1.1 Electric Vehicle Charging Stations (EVCS)
11B-812.8.2 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Five to Twenty-Five
Where five to twenty-five total EVCS are provided, one van accessible EVCS shall be identified by an ISA complying with Section 11B -703.7.2.1. The ...
Los Angeles Building Code > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-812 Electric Vehicle Charging Stations > 11B-812.8 Identification Signs > 11B-812.8.2 Five to Twenty-Five
11B-812.5.1 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Accessible Route to Building or Facility
EVCS complying with Section 11B -812 that serve a particular building or facility shall be located on an accessible route to an entrance complying ...
Los Angeles Building Code > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-812 Electric Vehicle Charging Stations > 11B-812.5 Accessible Routes > 11B-812.5.1 Accessible Route to Building or Facility