D105.3 Proximity to Building
JUMP TO FULL CODE CHAPTER
At least one of the required access routes meeting this condition shall be located within a minimum of 15 feet (4572 mm) and a maximum of 30 feet (9144 mm) from the building, and shall be positioned parallel to one entire side of the building.
Related Code Sections
D105.3 Fire Apparatus Access Roads, Proximity to Building
(9144 mm) from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire ...
Fire Code 2015 of New York State > D Fire Apparatus Access Roads > D105 Aerial Fire Apparatus Access Roads > D105.3 Proximity to Building
D105.3 Fire Apparatus Access Roads, Proximity to Building
mm) from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire ...
2020 Fire Code of NYS > D Fire Apparatus Access Roads > D105 Aerial Fire Apparatus Access Roads > D105.3 Proximity to Building
D105.3 Fire Apparatus Access Roads, Proximity to Building
(9144 mm) from the building, and shall be positioned parallel to one entire side of the building ...
2010 Fire Code of NY > D Fire Apparatus Access Roads > D105 Aerial Fire Apparatus Access Roads > D105.3 Proximity to Building
307.1.1 General Requirements, Dry Vegetation, Combustible Waste and Refuse
Combustible waste, refuse and large quantities of dry vegetation which by reason of their proximity to buildings or structures would constitute ...
2010 Property Maintenance Code of NY > 3 General Requirements > 307 Rubbish and Garbage > 307.1 Accumulation of Rubbish or Garbage > 307.1.1 Dry Vegetation, Combustible Waste and Refuse
P3002.2.1 Sanitary Drainage, Building Sewer Pipe Near the Water Service
The proximity of a building sewer to a water service shall comply with Section P2906.4.1 ...
2020 Residential Code of New York State > 30 Sanitary Drainage > P3002 Materials > P3002.2 Building Sewer > P3002.2.1 Building Sewer Pipe Near the Water Service