Buildings greater than 22 feet (6706 mm) in height with roof slopes less than 2.4 units vertical in 12 units horizontal (20-percent slope) shall be provided with a parapet, guards, fence, or combination thereof, not less than 42 inches (1067 mm) in height. Guards or fences may be located inward from the face of the exterior wall a distance not exceeding 6 feet (1828.8 mm). Guards or fences shall be of noncombustible material, except on buildings of Type V construction. Guards shall be constructed to comply with the requirements of Sections 1015 and 1607.8.
1510.8.1 Fences on Roofs Used for Recreational Purposes
Rooftops used for recreational purposes shall be provided with wire fencing at least 10 feet (3048 mm) in height. Openings in the fence shall not permit the passage of a 4-inch (101.6 mm) diameter sphere. Where ball games are played on rooftops the wire fencing shall be extended to provide an overhead closure.

Related Code Sections

1509.8 Roof Assemblies and Rooftop Structures, Protective Guards
Buildings greater than 22 feet (6706 mm) in height with roof slopes less than 2.4 units vertical in 12 units horizontal (20 percent slope) shall ...
1509.8 Roof Assemblies and Rooftop Structures, Protective Guards
Buildings greater than 22 feet (6706 mm) in height with roof slopes less than 2.4 units vertical in 12 units horizontal (20-percent slope) shall ...
1510.8 Roof Assemblies and Rooftop Structures, Protective Guards
be provided with a parapet, guards, fence, or combination thereof, not less than 42 inches (1067 mm) in height. Guards or fences may be located inward ...
§27-334 Fire Protection Construction Requirements, Protective Guards
Buildings that are more than twenty-two feet in height and have roofs that are flatter than twenty degrees to the horizontal shall be provided ...
§27-465 Special Uses and Occupancies, Railings
Substantial railings or protective guards of noncombustible materials shall be provided at the perimeter of all parking tiers, except where exterior ...