• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Article 11 Protective Devices and Fire Protection

§27 ‒ Housing Maintenance Code > 2 Maintenance, Services, and Utilities > 11 Protective Devices and Fire Protection
JUMP TO FULL CODE CHAPTER

§27-2041 Peepholes

In every dwelling the owner shall provide and maintain a peephole in the entrance door of each dwelling unit. Such peephole shall be located, as prescribed by the department, in such a place that the person in each dwelling unit may view from the inside any person immediately outside the entrance door. However, such peephole need not be installed in any tenant-occupied one- or two-family home where it is possible to see from the inside any person immediately outside the entrance door. This section shall not apply to hotels, apartment hotels, college or school dormitories, or owner-occupied dwelling units in one- and two-family homes.

§27-2042 Mirrors in Elevators

The owner of a multiple dwelling in which there are one or more self-service elevators shall affix and maintain in each such elevator a mirror which enables persons to view its interior before entering the same. The mirror shall meet such requirements as the department shall by regulation prescribe.

§27-2043 Locks in Dwelling Unit Doors

   a.   The owner of a dwelling shall provide a key lock in the entrance door to each dwelling unit and at least one key. In a class A multiple dwelling such door shall be equipped with a heavy duty latch set and a heavy duty dead bolt operable by a key from the outside and a thumb-turn from the inside.
   b.   Each dwelling unit entrance door in a class A multiple dwelling shall also be equipped with a chain door guard so as to permit partial opening of the door.

§27-2043.1 Window Guards

   a.   An owner of a multiple dwelling and an owner of a dwelling unit in a multiple dwelling owned as a condominium shall provide, install and maintain a window guard, in accordance with specifications established by the department of health and mental hygiene, on each window of each dwelling unit in which a child ten years of age or under resides, and on the windows, if any, in the public areas of a multiple dwelling in which such a child resides.
   b.   Subdivision a of this section shall not apply to a window that gives access to a fire escape or to a window that is a required means of egress from a dwelling unit on the first floor of a multiple dwelling.
   c.   No tenant or occupant of a dwelling unit, or other person, shall obstruct or interfere with the installation or maintenance of a window guard as required by subdivision a of this section nor shall any person remove such window guard.
   d.   No owner of a multiple dwelling and no owner of a dwelling unit in a multiple dwelling owned as a condominium shall refuse a written request of a tenant or occupant of a dwelling unit to provide, install and maintain a window guard, in accordance with specifications established by the department of health and mental hygiene, regardless of whether such provision, installation and maintenance is required pursuant to subdivision a of this section, except that this subdivision shall not apply to a window that gives access to a fire escape or to a window that is a required means of egress from a dwelling unit on the first floor of a multiple dwelling.
   e.   Any owner required to provide, install and maintain a window guard pursuant to subdivision a or d of this section who fails to provide, install or maintain a window guard shall be liable for a class C immediately hazardous violation. Notwithstanding any other provision of law to the contrary, the time within which to correct such violation shall be twenty-one days after service of the notice of violation.
   f.   Notwithstanding any other provision of law to the contrary, the department shall be the sole agency of the city authorized to seek a monetary penalty from an owner who is required to provide, install and maintain a window guard for failure to provide, install or maintain such window guard. Nothing in this section shall limit the authority of the department of health and mental hygiene to investigate a fall from any window or to issue an order to correct any condition that such department determines contributed to such fall.

§27-2044 Fire Protection in Certain Old Law Tenements

   a.   In every old law tenement which is less than four stories in height:
      (1)   Every door opening into any entrance hall or stair, or into any public hall connected therewith, shall be self-closing; every glazed opening or glazed panel in such a door shall be glazed with wire glass, and every transom opening upon any public hall shall be glazed with wire glass firmly secured in a closed position; and
      (2)   Every interior sash, or opening other than a door, in the walls or partitions of any such hall, and every window in any such hall not opening to the outer air, shall be removed and the openings closed up and fire-retarded; and
      (3)   The ceiling of the cellar, or if there is no cellar, of the basement or other lowest story, shall be fire-retarded unless such ceiling already has been plastered or covered in a manner satisfactory to the department with plasterboard or gypsumboard at least one-half inch in thickness.
   b.   In every old law tenement which is four stories or more in height:
      (1)   On all stories above the third story, every apartment door opening into any stair or into any public hall connected therewith, unless such stair or public hall is protected by an approved sprinkler system shall have a fire resistance rating of at least one hour. Existing door frames in good condition may be retained. All such doors shall comply with this requirement, not later than November second, nineteen hundred seventy-three.
      (2)   For all stories below the fourth story, any application for an alteration permit for alterations to be made in an apartment below the fourth story shall include the provision that every door of such apartment opening into any entrance hall, stair or into any public hall connected therewith, unless such entrance hall, stair or public hall is protected by an approved sprinkler system, shall have a fire resistance rating of at least one hour. Existing door frames in good condition may be retained.
      (3)   Where apartment doors having a fire resistance rating of at least one hour are required, every transom opening upon any entrance hall, stair or public hall connected therewith shall be sealed and fireretarded. All other transoms opening upon any entrance hall, stair or public hall connected therewith shall be glazed with wire glass and permanently sealed in a closed position.
      (4)   All doors opening into any entrance hall, stair or into any public hall connected therewith shall be self-closing; every glazed opening or glazed panel in such a door shall be glazed with wire glass.

§27-2045 Duties of Owner and Occupant With Respect to Installation and Maintenance of Smoke Detecting Devices in Class A Multiple Dwellings

Editor's note: this §27-2045 has been REPEALED AND REENACTED by  L.L. 2016/157, 12/6/2016, effective 5/1/2018.
   a.   It shall be the duty of the owner of a class A multiple dwelling which is required to be equipped with smoke detecting devices pursuant to section 907.2 of the New York city building code or sections 27-978, 27-979, 27-980 and 27-981 of the 1968 building code to:
      (1)   provide and install one or more approved and operational smoke detecting devices in each dwelling unit and replace such devices in accordance with article 312 of chapter 3 of title 28 of the administrative code of the city of New York. Such devices shall be installed at locations specified in reference standard 17-12 of the 1968 building code or section 907.2.10 of the New York city building code, as applicable.
      (2)   post a notice in a form approved by the commissioner in a common area of the building informing the occupants of such building (i) that the owner is required by law to install one or more approved and operational smoke detecting devices in each dwelling unit in the building and to periodically replace such devices upon the expiration of their useful life in accordance with article 312 of chapter 3 of title 28 of the administrative code of the city of New York and (ii) that each occupant is responsible for the maintenance and repair of such devices and for replacing any or all such devices which are stolen, removed, missing or rendered inoperable during the occupancy of such dwelling unit with a device meeting the requirements of article 312 of chapter 3 of title 28 of the administrative code of the city of New York.
      (3)   replace any smoke detecting device which has been stolen, removed, missing or rendered inoperable during a prior occupancy of the dwelling unit and which has not been replaced by the prior occupant prior to the commencement of a new occupancy of a dwelling unit with a device meeting the requirements of article 312 of chapter 3 of title 28 of the administrative code of the city of New York.
      (4)   replace within thirty calendar days after the receipt of written notice any such device which becomes inoperable within one year of the installation of such device due to a defect in the manufacture of such device and through no fault of the occupant of the dwelling unit.
      (5)   keep such records as the commissioner shall prescribe relating to the installation and maintenance of smoke detecting devices in the building, including records showing that such devices meet the requirements of article 312 of chapter 3 of title 28 of the administrative code of the city of New York, and make such records available to the commissioner upon request.
   b.   Notwithstanding the provisions of subdivision a of section 27-2005 of article one of this subchapter and subdivision c of section 27-2006 of article one of this subchapter, it shall be the sole duty of the occupant of each dwelling unit in a class A multiple dwelling in which a smoke detecting device has been provided and installed by the owner pursuant to the provisions of section 907.2 of the New York city building code or sections 27-978, 27-979, 27-980 and 27-981 of the 1968 building code to:
      (1)   keep and maintain such device in good repair; and
      (2)   replace any and all devices which are either stolen, removed, missing or rendered inoperable during the occupancy of such dwelling unit with a device meeting the requirements of article 312 of chapter 3 of title 28 of the administrative code of the city of New York.
   c.   Except as otherwise provided in paragraphs three and four of subdivision a of this section and article 312 of chapter 3 of title 28 of the administrative code of the city of New York, an owner of a class A multiple dwelling who has provided and installed a smoke detecting device in a dwelling unit pursuant to this section shall not be required to keep and maintain such device in good repair or to replace any such device which is stolen, removed, missing or rendered inoperable during the occupancy of such dwelling unit.
   d.   The occupant of a dwelling unit in which a battery-operated smoke detecting device is provided and installed pursuant to this section shall reimburse the owner a maximum of twenty-five dollars, or a maximum of fifty dollars where a combined smoke and carbon monoxide detecting device is installed, for the cost of providing and installing each such device. The occupant shall have one year from the date of installation to make such reimbursement.
   e.   For the purposes of this section, the term "class A" multiple dwelling shall include garden-type maisonette dwellings constructed before April eighteenth, nineteen hundred fifty-four and the term "garden-type maisonette dwellings" shall be defined as any dwelling project consisting of a series of dwelling units which together and in their aggregate are arranged or designed to provide three or more apartments, and are provided as a group collectively with all essential services such as, but not limited to, house sewers and heat, and which are operated as a unit under single ownership, notwithstanding that certificates of occupancy were issued for portions thereof as private dwellings. 
SEE MORE

Related Code Sections


§27-329 Fire Protection Construction Requirements, Opening Protectives
Opening protectives, including frames, self-closing devices, and hardware, shall be classified as to fire-protection rating in accordance ...
NYC 1968 Code (Vol I) > 5 Fire Protection Construction Requirements > 3 Fire-Resistance Requirements > §27-329 Opening Protectives
Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment [PDF] (page 1)
Opening Devices for Dry Pipe Valves for Fire-Protection Service (Revision 7/85)..1979 UL No. 1726 Automatic Drain Valves for Standpipe Systems (Revision ...
NYC 1968 Code (Vol II) [PDF] > Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment
909.5.2 Fire Protection Systems, Opening Protection
Openings in smoke barriers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system ...
NYC Building Code 2014 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.5 Smoke Barrier Construction > 909.5.2 Opening Protection
909.5.3 Fire Protection Systems, Opening Protection
Openings in smoke barriers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system ...
NYC Building Code 2022 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.5 Smoke Barrier Construction > 909.5.3 Opening Protection
Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment [PDF] (page 52)
Pressure-Reducing and Pressure-Control Valves for Fire-Protection Service. UL 1486-1979-Quick Opening Devices for Dry Pipe Valves for Fire-Protection ...
NYC 1968 Code (Vol II) [PDF] > Reference Standard 17 Fire, Alarms, Detection and Extinguishing Equipment
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING