18.1* Protection of Piping Against Damage Where Subject to Earthquakes
Go To Full Code Chapter
18.1.1
Where water-based fire protection systems are required to be protected against damage from earthquakes, the requirements of Chapter 18 shall apply, unless the requirements of 18.1.2 are met.
18.1.2
Alternative methods of providing earthquake protection of sprinkler systems based on a seismic analysis certified by a registered professional engineer such that system performance will be at least equal to that of the building structure under expected seismic forces shall be permitted.
18.1.3 Obstructions to Sprinklers
Braces and restraints shall not obstruct sprinklers and shall comply with the obstruction rules of Chapters 10 through 14.
Related Code Sections
18.1* Installation Requirements for Seismic Protection, Protection of Piping Against Damage Where Subject to Earthquakes
Where water-based fire protection systems are required to be protected against damage from earthquakes, the requirements of Chapter 18 shall apply ...
9.3 Hanging, Bracing, and Restraint of System Piping, Protection of Piping Against Damage Where Subject to Earthquakes
Where water-based fire protection systems are required to be protected against damage from earthquakes, the requirements of Section 9.3 shall apply ...
9.3 Hanging, Bracing, and Restraint of System Piping, Protection of Piping Against Damage Where Subject to Earthquakes
Where water-based fire protection systems are required to be protected against damage from earthquakes, the requirements of Section 9.3 shall apply ...
9.3.7 Hanging, Bracing, and Restraint of System Piping, Hangers and Fasteners Subject to Earthquakes
to earthquakes. Where seismic protection is provided ...
9.3.1* Hanging, Bracing, and Restraint of System Piping, General
Where water-based fire protection systems are required to be protected against damage from earthquakes, the requirements of Section 9.3 shall apply ...