Section 305 Protection of Pipes Andplumbing System Components
JUMP TO FULL CODE CHAPTER
Pipes passing through concrete or cinder walls and floors or other corrosive material shall be protected against external corrosion by a protective sheathing or wrapping or other means that will withstand any reaction from the lime and acid of concrete, cinder or other corrosive material. Sheathing or wrapping shall allow for movement including expansion and contraction of piping. Minimum wall thickness of material shall be 0.025 inch (0.64 mm).
Pipes passing through or under walls shall be protected from breakage.
Piping in a plumbing system shall be installed so as to prevent strains and stresses that exceed the structural strength of the pipe. Where necessary, provisions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement.
Annular spaces between sleeves and pipes shall be filled or tightly caulked in an approved manner. Annular spaces between sleeves and pipes in fire-resistance-rated assemblies shall be filled or tightly caulked in accordance with the building code.
Any pipe that passes under a footing or through a foundation wall shall be provided with a relieving arch, or a pipe sleeve pipe shall be built into the foundation wall. The sleeve shall be two pipe sizes greater than the pipe passing through the wall.
Water, soil and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision is made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6 inches (152 mm) below the frost line and not less than 12 inches (305 mm) below grade.
Deleted.
In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 11/2 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by steel shield plates. Such shield plates shall have a thickness of not less than 0.0575 inch (1.463 mm) (No. 16 gage). Such plates shall cover the area of the pipe where the member is notched or bored, and shall extend a minimum of 2 inches (51 mm) above sole plates and below top plates.
Components of a plumbing system installed along alleyways, driveways, parking garages or other locations exposed to damage shall be recessed into the wall or otherwise protected in an approved manner.
Related Code Sections
Section 305 General Regulations, Protection of Pipes Andplumbing System Components
be protected from breakage. Piping in a plumbing system ...
Ohio Plumbing Code 2011 > 3 General Regulations > 305 Protection of Pipes Andplumbing System Components
305.4 General Regulations, Sleeves
Annular spaces between sleeves and pipes shall be filled or tightly caulked in an approved manner. Annular spaces between sleeves and pipes in fire ...
Ohio Plumbing Code 2011 > 3 General Regulations > 305 Protection of Pipes Andplumbing System Components > 305.4 Sleeves
305.1 General Regulations, Corrosion
Pipes passing through concrete or cinder walls and floors or other corrosive material shall be protected against external corrosion by a protective ...
Ohio Plumbing Code 2011 > 3 General Regulations > 305 Protection of Pipes Andplumbing System Components > 305.1 Corrosion
305.2 General Regulations, Breakage
Pipes passing through or under walls shall be protected from breakage ...
Ohio Plumbing Code 2011 > 3 General Regulations > 305 Protection of Pipes Andplumbing System Components > 305.2 Breakage
305.7 General Regulations, Waterproofing of Openings
Joints at the roof and around vent pipes, shall be made water-tight by the use of lead, copper, galvanized steel, aluminum, plastic or other approved ...
Ohio Plumbing Code 2011 > 3 General Regulations > 305 Protection of Pipes Andplumbing System Components > 305.7 Waterproofing of Openings