1926.405(j)(4)(iv) Protection of Live Parts-All Voltages
JUMP TO FULL CODE CHAPTER
Stationary motors having commutators, collectors, and brush rigging located inside of motor end brackets and not conductively connected to supply circuits operating at more than 150 volts to ground need not have such parts guarded. Exposed live parts of motors and controllers operating at 50 volts or more between terminals shall be guarded against accidental contact by any of the following:
By installation in a room or enclosure that is accessible only to qualified persons;
By installation on a balcony, gallery, or platform, so elevated and arranged as to exclude unqualified persons; or
By elevation 8 feet (2.44 m) or more above the floor.
Where live parts of motors or controllers operating at over 150 volts to ground are guarded against accidental contact only by location, and where adjustment or other attendance may be necessary during the operation of the apparatus, insulating mats or platforms shall be provided so that the attendant cannot readily touch live parts unless standing on the mats or platforms.
Related Code Sections
1926.405(j)(4)(iv) Electrical, Protection of Live Parts-All Voltages
circuits operating at more than 150 volts to ground need not have such parts guarded. Exposed live parts of motors and controllers operating at 50 volts ...
OSHA 1926 Construction > K Electrical > 1926.405 Wiring Methods, Components, and Equipment for General Use > 1926.405(j) Equipment for General Use > 1926.405(j)(4) Motors > 1926.405(j)(4)(iv) Protection of Live Parts-All Voltages
1926.405(j)(5)(ii) Electrical, Operating Voltage
The operating voltage of exposed live parts of transformer installations shall be indicated by warning signs or visible markings on the equipment ...
OSHA 1926 Construction > K Electrical > 1926.405 Wiring Methods, Components, and Equipment for General Use > 1926.405(j) Equipment for General Use > 1926.405(j)(5) Transformers > 1926.405(j)(5)(ii) Operating Voltage
1926.960(c) Electric Power Transmission and Distribution, Live Work
3 The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges.
TABLE V-7 - DC LIVE ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.960 Working on or Near Exposed Energized Parts > 1926.960(c) Live Work
1926.966(e)(1)(iii)(B) Electric Power Transmission and Distribution,
The live parts are installed at a height, above ground and any other working surface, that provides protection at the voltage on the live parts ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.966 Substations > 1926.966(e) Guarding of Rooms and Other Spaces Containing Electric Supply Equipment > 1926.966(e)(1) When to Guard Rooms and Other Spaces > 1926.966(e)(1)(iii) > 1926.966(e)(1)(iii)(B)
1926.966(e)(1)(iii) Electric Power Transmission and Distribution,
protection at the voltage on the live parts corresponding to the protection provided by a 2.4-meter (8-foot) height at 50 volts ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.966 Substations > 1926.966(e) Guarding of Rooms and Other Spaces Containing Electric Supply Equipment > 1926.966(e)(1) When to Guard Rooms and Other Spaces > 1926.966(e)(1)(iii)