902.10 Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
JUMP TO FULL CODE CHAPTER
Non-direct-vent appliances installed in beauty shops, barber shops, or other facilities where chemicals that generate corrosive or
flammable products such as aerosol sprays are routinely
used shall be located in a mechanical equipment room separate or partitioned off from other areas with provisions for
combustion and dilution air from outdoors. Direct-vent appliances
in such facilities shall be installed in accordance with the appliance manufacturer's installation instructions. [NFPA 54:9.1.6.2]
Related Code Sections
902.12 Installation of Specific Appliances, Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
Non-direct-vent appliances installed in beauty shops, barber shops,
or other facilities where chemicals that generate corrosive or
flammable products ...
Los Angeles Mechanical Code > 9 Installation of Specific Appliances > 902.0 General > 902.12 Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
902.10 Installation of Specific Appliances, Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
Non-direct-vent appliances installed in beauty shops, barber shops, or other facilities where chemicals that generate corrosive or
flammable products ...
Los Angeles Mechanical Code > 9 Installation of Specific Appliances > 902.0 General > 902.10 Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
507.10 Water Heaters, Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
Non-direct-vent appliances installed in beauty shops, barber shops,
or other facilities where chemicals that generate corrosive or
flammable products ...
Los Angeles Plumbing Code > 5 Water Heaters > 507.0 Appliance and Equipment Installation Requirements > 507.10 Protection of Gas Appliances From Fumes or Gases Other Than Products of Combustion
505.1 Exhaust Systems, General
A mechanical ventilation or exhaust system
shall be installed to control, capture, and remove emissions generated from product use or handling where ...
Section 6104 Liquefied Petroleum Gases, Location of LP-gas Containers
of an underground LP-gas container shall be not less than 10 feet from a building or lot line of adjoining property that can be built upon. For other than ...