913.2.1 Protection of Fire Pump Rooms
JUMP TO FULL CODE CHAPTER
Fire pumps shall be located in rooms that are separated from all other areas of the building by 2-hour fire barriers constructed in accordance with Section 707 or 2-hour horizontal assemblies constructed in accordance with Section 711, or both.
Exceptions:
- In other than high-rise buildings, separation by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711, or both, shall be permitted in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
- Separation is not required for fire pumps physically separated in accordance with NFPA 20.
Related Code Sections
913.2.1 Fire Protection and Life Safety Systems, Protection of Fire Pump Rooms
Fire pumps shall be located in rooms that are separated from all other areas of the building by 2-hour fire barriers constructed in accordance ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 913 Fire Pumps > 913.2 Protection Against Interruption of Service > 913.2.1 Protection of Fire Pump Rooms
913.2.1 Fire Protection and Life Safety Systems, Protection of Fire Pump Rooms
Fire pumps shall be located in rooms that are separated from all other areas of the building by 2-hour fire barriers constructed in accordance ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 913 Fire Pumps > 913.2 Protection Against Interruption of Service > 913.2.1 Protection of Fire Pump Rooms
902.1 Fire Protection and Life Safety Systems, Pump and Riser Room Size
Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size
902.1 Fire Protection and Life Safety Systems, Pump and Riser Room Size
Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size
902.1.3 Fire Protection and Life Safety Systems, Environment
Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40°F (4°C). Heating units shall ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 902 Fire Pump and Riser Room Size > 902.1 Pump and Riser Room Size > 902.1.3 Environment