608.14.2 Protection of Backflow Preventers
JUMP TO FULL CODE CHAPTER
Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions or are protected from freezing by heat, insulation or both.
The termination of the piping from the relief port or air gap fitting of a backflow preventer shall discharge to an approved indirect waste receptor or to the outdoors where it will not cause damage or create a nuisance.
Related Code Sections
608.14.2 Water Supply and Distribution, Protection of Backflow Preventers
Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions or are protected from ...
Plumbing Code 2015 of New York State > 6 Water Supply and Distribution > 608 Protection of Potable Water Supply > 608.14 Location of Backflow Preventers > 608.14.2 Protection of Backflow Preventers
608.15.2 Water Supply and Distribution, Protection of Backflow Preventers
Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions or are protected from ...
2020 Plumbing Code of NYS > 6 Water Supply and Distribution > 608 Protection of Potable Water Supply > 608.15 Location of Backflow Preventers > 608.15.2 Protection of Backflow Preventers
P2902.6.2 Water Supply and Distribution, Protection of Backflow Preventers
Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions, or are protected by heat ...
2020 Residential Code of New York State > 29 Water Supply and Distribution > P2902 Protection of Potable Water Supply > P2902.6 Location of Backflow Preventers > P2902.6.2 Protection of Backflow Preventers
P2902.6.2 Water Supply and Distribution, Protection of Backflow Preventers
Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions, or are protected by heat ...
Residential Code 2015 of New York State > 29 Water Supply and Distribution > P2902 Protection of Potable Water Supply > P2902.6 Location of Backflow Preventers > P2902.6.2 Protection of Backflow Preventers
608.17.4 Water Supply and Distribution, Connections to Automatic Fire Sprinkler Systems and Standpipe Systems
The potable water supply to automatic fire sprinkler and standpipe systems shall be protected against backflow by a double check backflow prevention ...
2020 Plumbing Code of NYS > 6 Water Supply and Distribution > 608 Protection of Potable Water Supply > 608.17 Connections to the Potable Water System > 608.17.4 Connections to Automatic Fire Sprinkler Systems and Standpipe Systems