60.5.1.9 Protection From Vehicles
JUMP TO FULL CODE CHAPTER
Guard posts or other approved means shall be provided to protect the following where subject to vehicular damage:
- Storage tanks and connected piping, valves, and fittings
- Storage areas containing tanks or portable containers except where the exposing vehicles are powered industrial trucks used for transporting the hazardous materials
- Use areas [400:6.1.9.1]
Where guard posts are installed, the posts shall meet the following criteria:
- They shall be constructed of steel not less than 4 in. (102 mm) in diameter and concrete filled.
- They shall be spaced not more than 4 ft (1.2 m) between posts on center.
- They shall be set. not less than 3 ft (0.9 m) deep in a concrete footing of not less than a 15 in. (381 mm) diameter
- They shall be set. with the top of the posts not less than 3 ft (0.9 m) above ground.
- They shall be located not less than 5 ft (1.5 m) from the tank. [400:6.1.9.2]
Related Code Sections
(A) Special Equipment, Vehicles
Sign or outline lighting system equipment shall be at least 4.3 m (14 ft) above areas accessible to vehicles unless protected from physical damage ...
National Electrical Code 2014 of Delaware > 6 Special Equipment > 600 Electric Signs and Outline Lighting > 600.9 Location > (A) Vehicles
69.2.1.2.2.1 Liquefied Petroleum Gases and Liquefied Natural Gases,
Appurtenance protection from physical damage shall be provided by recessing, by protective housings, or by location on the vehicle. [ 58: 5.2.6.2(A)] ...
Fire Code 2015 of Delaware > 69 Liquefied Petroleum Gases and Liquefied Natural Gases > 69.2 LP-gas Equipment and Appliances > 69.2.1 Containers > 69.2.1.2 Portable Container Appurtenance Physical Damage Protection > 69.2.1.2.2 > 69.2.1.2.2.1
42.3.3.3.3.2.2 Refueling,
Vaults that are not resistant to damage from the impact of a motor vehicle shall be protected by collision barriers. [ 30: 25.5.2.2] ...
Fire Code 2015 of Delaware > 42 Refueling > 42.3 Storage of Liquids > 42.3.3 Storage of Liquids > 42.3.3.3 Vaults for Aboveground Tanks > 42.3.3.3.3* Construction and Installation of Storage Tank Vaults > 42.3.3.3.3.2 Installation Requirements > 42.3.3.3.3.2.2
66.25.5.2.2 Flammable and Combustible Liquids,
Vaults that are not resistant to damage from the impact of a motor vehicle shall be protected by collision barriers. [ 30: 25.5.2.2] ...
Fire Code 2015 of Delaware > 66 Flammable and Combustible Liquids > 66.25 Storage Tank Vaults > 66.25.5* Construction and Installation of Storage Tank Vaults > 66.25.5.2 Installation Requirements > 66.25.5.2.2
42.7.2.2.5.1 Refueling,
vehicle. This device shall be protected from tampering and physical damage. [ 30A: 9.2.2.5.1] ...
Fire Code 2015 of Delaware > 42 Refueling > 42.7 Operational Requirements > 42.7.2 Basic Requirements > 42.7.2.2 Tank Filling and Bulk Delivery > 42.7.2.2.5 > 42.7.2.2.5.1