1910.29(k) Protection From Falling Objects
Go To Full Code Chapter
1910.29(k)(1)
The employers must ensure toeboards used for falling object protection:
1910.29(k)(1)(i)
Are erected along the exposed edge of the overhead walking-working surface for a length that is sufficient to protect employees below.
1910.29(k)(1)(iii)
Do not have more than a 0.25-inch (0.5-cm) clearance or opening above the walking-working surface.
1910.29(k)(1)(iv)
Are solid or do not have any opening that exceeds 1 inch (3 cm) at its greatest dimension.
1910.29(k)(1)(v)
Have a minimum height of 2.5 inches (6 cm) when used around vehicle repair, service, or assembly pits. Toeboards may be omitted around vehicle repair, service, or assembly pits when the employer can demonstrate that a toeboard would prevent access to a vehicle that is over the pit.
1910.29(k)(1)(vi)
Are capable of withstanding, without failure, a force of at least 50 pounds (222 N) applied in any downward or outward direction at any point along the toeboard.
1910.29(k)(1)(ii)
Have a minimum vertical height of 3.5 inches (9 cm) as measured from the top edge of the toeboard to the level of the walking-working surface.
1910.29(k)(2)
The employer must ensure:
1910.29(k)(2)(i)
Where tools, equipment, or materials are piled higher than the top of the toeboard, paneling or screening is installed from the toeboard to the midrail of the guardrail system and for a length that is sufficient to protect employees below. If the items are piled higher than the midrail, the employer also must install paneling or screening to the top rail and for a length that is sufficient to protect employees below; and
1910.29(k)(2)(ii)
All openings in guardrail systems are small enough to prevent objects from falling through the opening.
1910.29(k)(3)
The employer must ensure canopies used for falling object protection are strong enough to prevent collapse and to prevent penetration by falling objects.
Related Code Sections
1910.28(c) Walking-Working Surfaces, Protection From Falling Objects
of subpart I of this part. In addition, the employer must protect employees from falling objects by implementing one or more of the following ...
1910.29(k) Walking-Working Surfaces, Protection From Falling Objects
The employers must ensure toeboards used for falling object protection ...
1910.29(k)(1)(ii) Walking-Working Surfaces,
Have a minimum vertical height of 3.5 inches (9 cm) as measured from the top edge of the toeboard to the level of the walking-working surface ...
1910.29(k)(3) Walking-Working Surfaces,
The employer must ensure canopies used for falling object protection are strong enough to prevent collapse and to prevent penetration by falling ...
1910.29(k)(2)(i) Walking-Working Surfaces,
Where tools, equipment, or materials are piled higher than the top of the toeboard, paneling or screening is installed from the toeboard ...