Openings and outlets shall be protected by an air gap between the opening and the fixture flood level rim as specified in Table 608.16.1. Openings and outlets equipped for hose connection shall be protected by means other than an air gap.
TABLE 608.16.1
MINIMUM REQUIRED AIR GAPS
FIXTURE MINIMUM AIR GAP
Away from a walla (inches) Close to a wall (inches)
Lavatories and other fixtures with effective openings not greater than 1/2 inch in diameter 1 11/2
Sinks, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter 11/2 21/2
Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter 2 3
Drinking water fountains, single orifice not greater than 7/16 inch in diameter or multiple orifices with a total area of 0.150 square inch (area of circle 7/16 inch in diameter) 1 11/2
Effective openings greater than 1 inch Two times the diameter of the effective opening Three times the diameter of the effective opening
For SI: 1 inch = 25.4 mm, 1 square inch = 645 mm2.
  1. Applicable where walls or obstructions are spaced from the nearest inside-edge of the spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.

Related Code Sections

608.15.1 Water Supply and Distribution, Protection by Air Gap
Openings and outlets shall be protected by an air gap between the opening and the fixture flood level rim as specified in Table 608.15.1. Openings ...
608.15.1 Water Supply and Distribution, Protection by Air Gap
Openings and outlets shall be protected by an air gap between the opening and the fixture flood level rim as specified in Table 608.15.1. Openings ...
608.16.1 Water Supply and Distribution, Protection by Air Gap
Openings and outlets shall be protected by an air gap between the opening and the fixture flood level rim as specified in Table 608.16.1. Openings ...
409.2 Fixtures, Faucets and Fixture Fittings, Water Connection
The water supply to a dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608 ...
P2717.1 Plumbing Fixtures, Protection of Water Supply
The water supply to a dishwasher shall be protected against backflow by an air gap complying with ASME A112.1.3 or A112.1.2 that is installed ...