608.16.4 Protection by a Vacuum Breaker
JUMP TO FULL CODE CHAPTER
Openings and outlets shall be protected by atmospheric-type or pressure-type vacuum breakers. The critical level of the vacuum breaker shall be set not less than 6 inches (152 mm) above the flood level rim of the fixture or device. Fill valves shall be set in accordance with Section 415.3.1. Vacuum breakers shall not be installed under exhaust hoods or similar locations that will contain toxic fumes or vapors. Pipe-applied vacuum breakers shall be installed not less than 6 inches (152 mm) above the flood level rim of the fixture, receptor or device served.
Approved deck-mounted or equipment-mounted vacuum breakers and faucets with integral atmospheric vacuum breakers or spill-resistant vacuum breaker assemblies shall be installed in accordance with the manufacturer's instructions and the requirements for labeling with the critical level not less than 1 inch (25 mm) above the flood level rim.
Sillcocks, hose bibbs, wall hydrants and other openings with a hose connection shall be protected by an atmospheric-type or pressure-type vacuum breaker or a permanently attached hose connection vacuum breaker.
Exceptions:
- This section shall not apply to water heater and boiler drain valves that are provided with hose connection threads and that are intended only for tank or vessel draining.
- This section shall not apply to water supply valves intended for connection of clothes washing machines where backflow prevention is otherwise provided or is integral with the machine.
Related Code Sections
1402.3.2 Solar Thermal Systems, Vacuum
be protected with vacuum relief valves ...
Mechanical Code 2018 of Colorado > 14 Solar Thermal Systems > 1402 Design and Installation > 1402.3 Pressure and Temperature > 1402.3.2 Vacuum
1402.5.2 Solar Systems, Vacuum
or shall be protected with vacuum relief valves ...
Mechanical Code 2015 of Colorado > 14 Solar Systems > 1402 Installation > 1402.5 Equipment > 1402.5.2 Vacuum
(A) Wiring and Protection, Where Required
Where oil switches or air, oil, vacuum, or sulfur hexafluoride circuit breakers constitute the service disconnecting means, an isolating switch ...
National Electrical Code 2020 of Colorado > 2 Wiring and Protection > 230 Services > 230.204 Isolating Switches > (A) Where Required
Part VII Wiring and Protection, Circuit Breakers
National Electrical Code 2020 of Colorado > 2 Wiring and Protection > 240 Overcurrent Protection > VII Circuit Breakers
225.51 Wiring and Protection, Isolating Switches
Where oil switches or air, oil, vacuum, or sulfur hexafluoride circuit breakers constitute a building disconnecting means, an isolating switch ...
National Electrical Code 2020 of Colorado > 2 Wiring and Protection > 225 Outside Branch Circuits and Feeders > 225.51 Isolating Switches