407.3.3 Projections in Corridors
JUMP TO FULL CODE CHAPTER
In Group I-2 nursing homes, where the corridor width is a minimum of 96 inches (2440 mm), projections shall be permitted for furniture where all of the following conditions are met:
- The furniture is attached to the floor or to the wall.
- The furniture does not reduce the clear width of the corridor to less than 72 inches (1830 mm) except where other encroachments are permitted in accordance with Section 1005.7.
- The furniture is positioned on only one side of the corridor.
- Each arrangement of furniture is 50 square feet (4.6 square meters) maximum in area.
- Furniture arrangements are separated by 10 feet (3050 mm) minimum.
- Placement of furniture is considered as part of the fire and safety plans in accordance with Section 1001.4.
Related Code Sections
407.3.3 Special Detailed Requirements Based on Use and Occupancy, Projections in Corridors
In Group I-2 nursing homes, where the corridor width is a minimum of 96 inches (2440 mm), projections shall be permitted for furniture where all ...
Ohio Building Code 2011 > 4 Special Detailed Requirements Based on Use and Occupancy > 407 Group I-2 > 407.3 Corridor Walls > 407.3.3 Projections in Corridors
407.4.3 Special Detailed Requirements Based on Use and Occupancy, Projections in Nursing Home Corridors
In Group I-2, Condition 1, occupancies, where the corridor width is a minimum of 96 inches (2440 mm), projections shall be permitted for furniture ...
Ohio Building Code 2017 > 4 Special Detailed Requirements Based on Use and Occupancy > 407 Group I-2 > 407.4 Means of Egress > 407.4.3 Projections in Nursing Home Corridors
3405.5.1 Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids, Corridor Installations
(iv) The minimum corridor width shall be 72 inches (1829 mm). (v) Projections into a corridor shall be in accordance with paragraph (C)(3)(c ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids > 3405 Dispensing, Use, Mixing and Handling > 3405.5 Alcohol-Based Hand Rubs Classified as Class I or II Liquids > 3405.5.1 Corridor Installations
5705.5.1 Ohio Administrative Code 1301:7-7-57 Flammable and Combustible Liquids, Corridor Installations
). Projections into a corridor shall be in accordance with paragraph (C)(3)(c)(1003.3.3) of rule 1301:7-7-10 of the Administrative Code ...
2017 Ohio Fire Code > Ohio Administrative Code 1301:7-7-57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.5 Alcohol-Based Hand Rubs Classified as Class I or II Liquids > 5705.5.1 Corridor Installations
1005.4 Means of Egress, Other Projections
Handrail projections shall be in accordance with the provisions of Section 1012.8. Other nonstructural projections such as trim and similar ...