311.3 Prohibited Source
JUMP TO FULL CODE CHAPTER
Outside or return air for a heating
or cooling air system shall not be taken from the following locations:
- Less than 10 feet (3048 mm) in distance from an appliance vent outlet, a vent opening of a plumbing drainage system, or the discharge outlet of an exhaust fan, unless the outlet is 3 feet (914 mm) above the outside-air inlet.
- Less than 10 feet (3048 mm) above the surface of an abutting public way, sidewalk, street, alley, or driveway.
- A hazardous or insanitary location, or a refrigeration machinery room as defined in this code.
- An area, the volume of which is less than 25 percent of the
entire volume served by such system, unless there is a permanent
opening to an area the volume of which is equal to
25 percent of the entire volume served.
Exception: Such openings where used for a heating or cooling air system in a dwelling unit shall be permitted to be reduced to not less than 50 percent of the required area, provided the balance of the required return air is taken from a room or hall having not less than three doors leading to other rooms served by the furnace. - A closet, bathroom, toilet room, or kitchen.
- Rooms or spaces containing a fuel-burning appliance
therein. Where such room or space serves as source of
return-air.
Exceptions:- This shall not apply to fireplaces, fireplace appliances, residential cooking appliances, direct-vent appliances, enclosed furnaces, and domestic-type clothes dryers installed within the room or space.
- This shall not apply to a gravity-type or listed vented wall heating or cooling air system.
- This shall not apply to a blower-type heating or cooling
air system installed in accordance with the following
requirements:
- Where the return air is taken from a room or space having a volume exceeding 1 cubic foot (0.03 m3) for each 10 Btu/h (0.003 kW) fuel input rating of fuel-burning appliances therein.
- Not less than 75 percent of the supply air is discharged back into the same room or space.
- Return-air inlets shall not be located within 10 feet (3048 mm) from an appliance firebox or draft diverter in the same enclosed room or confined space.
Related Code Sections
1202.1 Hydronics, Prohibited Sources
Hydronic systems or parts
thereof, shall be constructed in such a manner that polluted,
contaminated water, or substances shall not enter a portion ...
California Mechanical Code 2016 > 12 Hydronics > 1202.0 Protection of Potable Water Supply > 1202.1 Prohibited Sources
1202.1 Hydronics, Prohibited Sources
Hydronic systems or parts
thereof shall be constructed in such a manner that polluted,
contaminated water or substances shall not enter a portion ...
California Mechanical Code 2019 > 12 Hydronics > 1202.0 Protection of Potable Water Supply > 1202.1 Prohibited Sources
311.3 General Regulations, Prohibited Source
appliance
therein. Where such room or space serves as source of
return-air.
Exceptions:
This shall not apply to fireplaces, fireplace ...
California Mechanical Code 2019 > 3 General Regulations > 311.0 Heating or Cooling Air System > 311.3 Prohibited Source
311.3 General Regulations, Prohibited Source
therein. Where such room or space serves as source of return-air.
Exceptions:
This shall not apply to fireplaces, fireplace appliances ...
California Mechanical Code 2016 > 3 General Regulations > 311.0 Heating or Cooling Air System > 311.3 Prohibited Source
6107.2 Liquefied Petroleum Gases, Smoking and Other Sources of Ignition
of transfer, while filling operations are in progress at LP-gas containers or vehicles, shall be prohibited. Control of other sources of ignition ...
California Fire Code 2019 > 61 Liquefied Petroleum Gases > 6107 Safety Precautions and Devices > 6107.2 Smoking and Other Sources of Ignition