507.5.3 Private Fire Service Mains and Water Tanks
JUMP TO FULL CODE CHAPTER
Private fire service mains and water tanks shall be periodically inspected, tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5.
- Private fire hydrants of all types: Inspection annually and after each operation; flow test and maintenance annually.
- Fire service main piping: Inspection of exposed, annually; flow test every 5 years.
- Fire service main piping strainers: Inspection and maintenance after each use.
Records of inspections, testing and maintenance shall be maintained.
Related Code Sections
507.5.3 Fire Service Features, Private Fire Service Mains and Water Tanks
Private fire service mains and water tanks shall be periodically inspected, tested and maintained in accordance with California Code of Regulations ...
California Fire Code 2019 > 5 Fire Service Features > 507 Fire Protection Water Supplies > 507.5 Fire Hydrant Systems > 507.5.3 Private Fire Service Mains and Water Tanks
507.5.3 Fire Service Features, Private Fire Service Mains and Water Tanks
Private fire service mains and water tanks shall be periodically inspected, tested and maintained in accordance with California Code of Regulations ...
California Fire Code 2016 > 5 Fire Service Features > 507 Fire Protection Water Supplies > 507.5 Fire Hydrant Systems > 507.5.3 Private Fire Service Mains and Water Tanks
507.5 Fire Service Features, Fire Hydrant Systems
service mains and water tanks shall be periodically inspected, tested and maintained in accordance with California Code of Regulations, Title 19 ...
California Fire Code 2016 > 5 Fire Service Features > 507 Fire Protection Water Supplies > 507.5 Fire Hydrant Systems
507.2.1 Fire Service Features, Private Fire Service Mains
Private fire service mains and appurtenances shall be installed in accordance with NFPA 24 as amended in Chapter 80 ...
California Fire Code 2016 > 5 Fire Service Features > 507 Fire Protection Water Supplies > 507.2 Type of Water Supply > 507.2.1 Private Fire Service Mains
507.2.1 Fire Service Features, Private Fire Service Mains
Private fire service mains and appurtenances shall be installed in accordance with NFPA 24 as amended in Chapter 80 ...
California Fire Code 2019 > 5 Fire Service Features > 507 Fire Protection Water Supplies > 507.2 Type of Water Supply > 507.2.1 Private Fire Service Mains