909.20.7.1 Pressurization Systems
Go To Full Code Chapter
Smokeproof enclosure pressurization systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring and ductwork shall comply with one of the following:
- Equipment, control wiring, power wiring and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
- Equipment, control wiring, power wiring and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
- Equipment, control wiring, power wiring and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
Exception:
- Control wiring and power wiring located outside of a 2-hour fire barrier construction shall be protected using any one of the following methods:
- Cables used for survivability of required critical circuits shall be listed in accordance with UL 2196 and shall have a fire-resistance rating of not less than 2 hours.
- Where encased with not less than 2 inches (51 mm) of concrete.
- Electrical circuit protective systems shall have a fire-resistance rating of not less than 2 hours. Electrical circuit protective systems shall be installed in accordance with their listing requirements.
Related Code Sections
5705.2.2 Flammable and Combustible Liquids, Pressured Systems
that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank ...
5705.2.2 Flammable and Combustible Liquids, Pressured Systems
that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank ...
5705.2.2 Flammable and Combustible Liquids, Pressured Systems
that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank ...
909.20.4.3.1 Fire Protection Systems, Pressurization Systems
Smokeproof enclosure pressurization systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring ...
909.20.6.1 Fire Protection and Life Safety Systems, Pressurization Systems
Smokeproof enclosure pressurization systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring ...