// CODE SNIPPET
5705.2.2 Pressured Systems
JUMP TO FULL CODE CHAPTER
Where gases are introduced to provide for transfer of Class I liquids, or Class II and III liquids transferred at temperatures at or above their flash points by pressure, only inert gases shall be used. Controls, including pressure relief devices, shall be provided to limit the pressure so that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank or container are used, the tank or container shall be a pressure vessel approved for the intended use. Air or oxygen shall not be used for pressurization.
Exception: Air transfer of Class II and III liquids at temperatures below their flash points.
Exception: Air transfer of Class II and III liquids at temperatures below their flash points.
Related Code Sections
3405.2.2 Flammable and Combustible Liquids, Pressured Systems
that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank ...
2010 Fire Code of NY > 34 Flammable and Combustible Liquids > 3405 Dispensing, Use, Mixing and Handling > 3405.2 Liquid Transfer > 3405.2.2 Pressured Systems
5705.2.2 Flammable and Combustible Liquids, Pressured Systems
that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank ...
Fire Code 2015 of New York State > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.2 Liquid Transfer > 5705.2.2 Pressured Systems
5705.2.2 Flammable and Combustible Liquids, Pressured Systems
that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank ...
2020 Fire Code of NYS > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.2 Liquid Transfer > 5705.2.2 Pressured Systems
707.14.2.5 Fire-Resistance-Rated Construction, Activation of Pressurization System
The elevator pressurization system shall be activated upon activation of the building fire alarm system or upon activation of the elevator lobby ...
2010 Building Code of NY > 7 Fire-Resistance-Rated Construction > 707 Shaft Enclosures > 707.14 Elevator, Dumbwaiter and Other Hoistways > 707.14.2 Enclosed Elevator Lobby Pressurization Alternative > 707.14.2.5 Activation of Pressurization System
909.21.6 Fire Protection and Life Safety Systems, Activation of Pressurization System
The elevator pressurization system shall be activated upon activation of either the building fire alarm system or the elevator lobby smoke detectors ...
2020 Building Code of New York State > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.21 Elevator Hoistway Pressurization Alternative > 909.21.6 Activation of Pressurization System