// CODE SNIPPET
705.3 Pressure Tests
JUMP TO FULL CODE CHAPTER
A hydrostatic or pneumatic leak test shall be performed. Testing of hydrogen piping systems shall utilize testing procedures identified in ASME B31.12 or other approved methods, provided that the testing is performed in accordance with the minimum provisions specified in Sections 705.3.1 through 705.4.1.
The hydrostatic test pressure shall be not less than one-and-one-half times the maximum working pressure, and not less than 100 psig (689.5 kPa gauge).
The pneumatic test pressure shall be not less than one-and-one-half times the maximum working pressure for systems less than 125 psig (862 kPa gauge) and not less than 5 psig (34.5 kPa gauge), whichever is greater. For working pressures at or above 125 psig (862 kPa gauge), the pneumatic test pressure shall be not less than 110 percent of the maximum working pressure.
Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Deionized water shall be utilized to perform hydrostatic pressure testing and shall be obtained from a potable source. The medium utilized to perform pneumatic pressure testing shall be air, nitrogen, carbon dioxide or an inert gas; oxygen shall not be used.
The minimum test duration shall be 1/2 hour. The test duration shall be not less than 1/2 hour for each 500 cubic feet (14.2 m3) of pipe volume or fraction thereof. For piping systems having a volume of more than 24,000 cubic feet (680 m3), the duration of the test shall not be required to exceed 24 hours. The test pressure required in Sections 705.3.1 and 705.3.2 shall be maintained for the entire duration of the test.
Gauges used for testing shall be as follows:
- Tests requiring a pressure of 10 psig (68.95 kPa gauge) or less shall utilize a testing gauge having increments of 0.10 psi (0.6895 kPa) or less.
- Tests requiring a pressure greater than 10 psig (68.98 kPa gauge) but less than or equal to 100 psig (689.5 kPa gauge) shall utilize a testing gauge having increments of 1 psi (6.895 kPa) or less.
Tests requiring a pressure greater than 100 psig (689.5 kPa gauge) shall utilize a testing gauge having increments of 2 psi (13.79 kPa) or less.
Exception: Measuring devices having an equivalent level of accuracy and resolution shall be permitted where specified by the design engineer and approved by the code official.
Pipe joints, including welds, shall be left exposed for examination during the test.
Expansion joints shall be provided with temporary restraints, if required, for the additional thrust load under test.
Where the piping system is connected to appliances, equipment or components designed for operating pressures of less than the test pressure, such appliances, equipment and components shall be isolated from the piping system by disconnecting them and capping the outlet(s).
Where the piping system is connected to appliances, equipment or components designed for operating pressures equal to or greater than the test pressure, such appliances, equipment and components shall be isolated from the piping system by closing the individual appliance, equipment or component shutoff valve(s).
Related Code Sections
705.3 Gaseous Hydrogen Systems, Pressure Tests
through 705.4.1. The hydrostatic test pressure shall ...
Fuel Gas Code 2015 of Colorado > 7 Gaseous Hydrogen Systems > 705 (IFGC) Testing of Hydrogen Piping Systems > 705.3 Pressure Tests
705.3 Gaseous Hydrogen Systems, Pressure Tests
through 705.4.1. The hydrostatic test pressure shall ...
Fuel Gas Code 2018 of Colorado > 7 Gaseous Hydrogen Systems > 705 (IFGC) Testing of Hydrogen Piping Systems > 705.3 Pressure Tests
716.8 Sanitary Drainage, Pressure Testing
The replacement piping system as well as the connections to the replacement piping shall be tested in accordance with Section 312 ...
Plumbing Code 2018 of Colorado > 7 Sanitary Drainage > 716 Replacement of Underground Building Sewers and Building Drains by Pipe-Bursting Methods > 716.8 Pressure Testing
717.8 Sanitary Drainage, Pressure Testing
The replacement piping system as well as the connections to the replacement piping shall be tested in accordance with Section 312 ...
Plumbing Code 2015 of Colorado > 7 Sanitary Drainage > 717 Replacement of Underground Sewers by Pipe-Bursting Methods > 717.8 Pressure Testing
406.4.1 Gas Piping Installations, Test Pressure
The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 kPa gauge ...
Fuel Gas Code 2015 of Colorado > 4 Gas Piping Installations > 406 (IFGS) Inspection, Testing and Purging > 406.4 Test Pressure Measurement > 406.4.1 Test Pressure