5503.3 Pressure Relief Vent Piping
JUMP TO FULL CODE CHAPTER
Pressure relief device vent piping shall have a cross-sectional area not less than that of the pressure relief device vent opening and shall be arranged so as not to restrict the flow of escaping gas.
Pressure relief device vent piping and drains in vent lines shall be arranged so that escaping gas will discharge unobstructed to the open air and not impinge on personnel, containers, equipment and adjacent structures or enter enclosed spaces. Pressure relief device vent lines shall be installed in such a manner to exclude or remove moisture and condensation and prevent malfunction of the pressure relief device because of freezing or ice accumulation.
Related Code Sections
5503.3 Cryogenic Fluids, Pressure Relief Vent Piping
Pressure relief vent-piping systems shall be constructed and arranged so as to remain functional and direct the flow of gas to a safe location ...
2017 LA City Fire Code > 55 Cryogenic Fluids > 5503 General Requirements > 5503.3 Pressure Relief Vent Piping
5307.4.2 Compressed Gases, Equipment
Pressure relief, vent piping, fill indicators,
fill connections, vent terminations, piping system,
and the storage, use, and handling of the carbon ...
2017 LA City Fire Code > 53 Compressed Gases > 5307 Compressed Gases Not Otherwise Regulated > 5307.4 Carbon Dioxide Enrichment Systems > 5307.4.2 Equipment
5303.3.5 Compressed Gases, Freeze Protection
Pressure relief devices or vent piping shall be designed or located so that moisture cannot collect and freeze in a manner that would interfere ...
2017 LA City Fire Code > 53 Compressed Gases > 5303 General Requirements > 5303.3 Pressure Relief Devices > 5303.3.5 Freeze Protection