// CODE SNIPPET
1316.3 Pressure Gauges
JUMP TO FULL CODE CHAPTER
Pressure and vacuum indicators shall be readable from a standing position. Pressure and vacuum indicators shall be provided at the following locations:
- Adjacent to the alarm-initiating device for source mainline pressure and vacuum alarms in the master alarm system.
- At or in area alarm panels to indicate the pressure, vacuum, or both at the alarm activating device for each system that is monitored by the panel.
- On the station outlet or inlet side of zone valves.
[NFPA 99:5.1.8.2.1, 5.1.8.2.2]
Related Code Sections
1316.3 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Pressure Gauges
Pressure and vacuum indicators shall be readable from a standing position. Pressure and vacuum indicators shall be provided at the following ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1316.0 Pressure-Regulating Equipment > 1316.3 Pressure Gauges
1003.3 Boilers and Pressure Vessels, Gauges
A steam boilers shall be provided with a pressure
gauge and a water level glass. A water boilers shall be
provided with a pressure gauge ...
California Mechanical Code 2016 > 10 Boilers and Pressure Vessels > 1003.0 Detailed Requirements > 1003.3 Gauges
1003.3 Boilers and Pressure Vessels, Gauges
Steam boilers shall be provided with a
pressure gauge and a water level glass. Water boilers shall be
provided with a pressure gauge ...
California Mechanical Code 2019 > 10 Boilers and Pressure Vessels > 1003.0 Detailed Requirements > 1003.3 Gauges
3125B.2 [DPH] Public Pools, Gauges
A pressure and vacuum gauge shall be provided for each pump system. Each gauge shall have a scale range approximately 1 1 / 4 times the maximum ...
California Building Code 2016 (Vol 1 & 2) > 31B [DPH] Public Pools > 3125B Recirculation Piping System and Components > 3125B.2 Gauges
5.508.2.2.1.1 Nonresidential Mandatory Measures, Pressure Detection
A pressure gauge, pressure transducer or other device shall be installed in the space between the rupture disc and the relief valve inlet to indicate ...
California Green Building Standards Code 2019 > 5 Nonresidential Mandatory Measures > 5.508 Outdoor Air Quality > 5.508.2 Supermarket Refrigerant Leak Reduction > 5.508.2.2 Valves > 5.508.2.2.1 Pressure Relief Valves > 5.508.2.2.1.1 Pressure Detection