Where a specific design is not provided, concrete or masonry-unit footings supporting walls of light-frame construction shall be permitted to be designed in accordance with Table 1809.7.
TABLE 1809.7
PRESCRIPTIVE FOOTINGS SUPPORTING WALLS OF LIGHT-FRAME CONSTRUCTIONa, b, c, d, e
NUMBER OF FLOORS SUPPORTED BY THE FOOTINGf WIDTH OF FOOTING (inches) THICKNESS OF FOOTING (inches)
1 12 6
2 15 6
3 18 8g
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
  1. Depth of footings shall be in accordance with Section 1809.4.
  2. The ground under the floor shall be permitted to be excavated to the elevation of the top of the footing.
  3. Interior stud-bearing walls shall be permitted to be supported by isolated footings. The footing width and length shall be twice the width shown in this table, and footings shall be spaced not more than 6 feet on center.
  4. See Section 1905 for additional requirements for concrete footings of structures assigned to Seismic Design Category C, D, E or F.
  5. For thickness of foundation walls, see Section 1807.1.6.
  6. Footings shall be permitted to support a roof in addition to the stipulated number of floors. Footings supporting roof only shall be as required for supporting one floor.
  7. Plain concrete footings for Group R-3 occupancies shall be permitted to be 6 inches thick.

Related Code Sections

1809.7 Soils and Foundations, Prescriptive Footings for Light-Frame Construction
Where a specific design is not provided, concrete or masonry-unit footings supporting walls of light-frame construction shall be permitted ...
1809.7 Soils and Foundations, Prescriptive Footings for Light-Frame Construction
Where a specific design is not provided, concrete or masonry-unit footings supporting walls of light-frame construction shall be permitted ...
2211.1.2 Steel, Prescriptive Framing
Detached one- and two-family dwellings and townhouses, less than or equal to three stories above grade plane, shall be permitted to be constructed ...
2211.1.2 Steel, Prescriptive Framing
Detached one- and two-family dwellings and townhouses, less than or equal to three stories above grade plane, shall be permitted to be constructed ...
2308.3 Wood, Foundations and Footings
Foundations and footings shall be designed and constructed in accordance with Chapter 18. Connections to foundations and footings shall comply ...