// CODE SNIPPET
4.2.0.1 Preliminary Screening
JUMP TO FULL CODE CHAPTER
All welded steel moment frame structures shall undergo a detailed frame joint evaluation if the building is located at a site that has experienced the following:
- An earthquake of magnitude greater than or equal to 6.5 that produced ground motion in excess of 0.20 g; or
- An earthquake that generated ground motion in excess of 0.30 g.
The ground motion estimates shall be based on actual instrumental recordings in the vicinity of the building. When such ground motion records are not available, ground motion estimates may be based on empirical or analytical techniques. All ground motion estimates shall reflect the site-specific soil conditions.
Related Code Sections
4.2.0.1 Seismic Evaluation Procedures for Hospital Buildings, Preliminary Screening
All welded steel moment frame structures shall undergo a detailed frame joint evaluation if the building is located at a site that has experienced ...
California Administrative Code 2019 > 6 Seismic Evaluation Procedures for Hospital Buildings > 4 Procedures for Moment-Resisting Systems > 4.2 Steel Moment Frames > 4.2.0.1 Preliminary Screening
4.2.0.1 Seismic Evaluation Procedures for Hospital Buildings, Preliminary Screening
All welded steel moment frame structures shall undergo a detailed frame joint evaluation if the building is located at a site that has experienced ...
California Administrative Code 2016 > 6 Seismic Evaluation Procedures for Hospital Buildings > 4 Procedures for Moment-Resisting Systems > 4.2 Steel Moment Frames > 4.2.0.1 Preliminary Screening
104.2.2 Scope and Administration, Preliminary Meeting
on the circumstances agreed on at the preliminary meeting. The design professional shall notify the code official if any potential noncompliance ...
California Existing Building Code 2019 > 1 Scope and Administration > 104 Duties and Powers of Code Official > 104.2 Applications and Permits > 104.2.2 Preliminary Meeting
104.2.2 Scope and Administration, Preliminary Meeting
on the circumstances agreed upon at the preliminary meeting. The design professional shall notify the code official if any potential nonconformance ...
California Existing Building Code 2016 > 1 Scope and Administration > 104 Duties and Powers of Code Official > 104.2 Applications and Permits > 104.2.2 Preliminary Meeting
109.2 Scope and Administration, Preliminary Inspection
Before issuing a permit, the code official is authorized to examine or cause to be examined buildings and sites for which an application has been ...
California Existing Building Code 2019 > 1 Scope and Administration > 109 Inspections > 109.2 Preliminary Inspection