• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects General Contractor Building Official & Plans Examiner Inspectors Owner Subcontractors Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

2319.17.2 Prefabricated Wood Trusses

2017 FBC - Building, 6th edition > 23 Wood > 2319 High-Velocity Hurricane Zones— Horizontal Framing > 2319.17 Wood Trusses > 2319.17.2 Prefabricated Wood Trusses
JUMP TO FULL CODE CHAPTER
Prefabricated wood trusses shall comply with this section.

2319.17.2.1 Design

2319.17.2.1.1

Prefabricated wood trusses shall be designed by a registered professional engineer (delegated engineer) and fabricated in accordance with the National Design Standard for Metal Plate Connected Wood Truss Construction of the Truss Plate Institute (TPI). The truss system designer (delegated engineer) shall prepare the truss system shop drawings. Such shop drawings shall be submitted to the building official for review and approval. The shop drawings shall meet the following requirements:

  1. All shop drawings shall be in conformity with the architect or engineer of record framing plans unless prior written approval is obtained from the architect or engineer of record. If reframing is approved, the architect or engineer of record shall resubmit revised framing plans to the building official after receiving updated plans from the delegated engineer showing all adjustments necessary to safely transmit all applied loads to the foundation.
  2. Permanent bracing of individual truss members may be required on certain members of the trusses to prevent the members from buckling in the plane normal to the trusses (buckling in the narrow direction). This bracing shall be designed for both upward and downward loads and shall be shown on the individual truss drawings (truss engineering usually shown on 81/2-inch by 11-inch (216 mm by 279 mm) sheets ("A" size drawings). The design of this bracing shall be the responsibility of the delegated engineer. The contractor shall be responsible for seeing that this bracing is properly installed. This bracing may be in the form of (but not limited to) "T" bracing of an individual member, or lateral bracing of a series of members common to a number of trusses. Where lateral bracing is used, this bracing shall be restrained against lateral movement, in accordance with details provided by the delegated engineer or by the architect or professional engineer of record. All details and sections required to show the size and connections of all secondary members will be supplied on the delegated engineering plans and shall show all framing, connections and bracing on one or more primary plans of minimum size 24 inches by 36 inches (610 mm by 914 mm).
  3. A size 81/2-inches by 11-inches (216 mm by 279 mm) cut sheets showing individual member design shall also be furnished to the architect or engineer of record so that all gravity and uplift loads shown on these cut sheets can be transferred to the primary plans.
  4. The size and location of all plates at each joint shall be shown on the truss design drawings.
  5. The connection between trusses shall be detailed in the shop drawings. Hip sets shall be detailed in a manner to indicate all connections according to engineering drawings for the attachment of skewed members.
  6. Truss design drawings shall indicate the support and minimum bearing of the roof structural system, the permanent cross/lateral bracing, bracing to transfer member buckling forces to the structure and all bracing and anchorage required to resist uplift and lateral forces.
  7. Flat and floor trusses must be clearly marked so that they will be installed right side up. These marks must remain after the flooring, sheathing and insulation have been installed.

The intent of the above requirements is to provide all information on framing, connections and bracing on one composite set of plans approved by the architect or engineer of record to aid in the review, approval and field inspections for the portion of the property.

2319.17.2.1.2

Trusses shall be designed for wind loads in accordance with Chapter 16 (High-Velocity Hurricane Zones), uniformly distributed live, dead and concentrated loads, and such loads shall be indicated on the roof framing plans and the truss design drawings. Where a girder or truss is subjected to concentrated loads or any unusual loading condition, such conditions must be clearly indicated on the roof framing plans and on the truss design drawings. Where truss members have been cut, shifted or altered in any manner to meet construction needs or for any other reason, additional drawings and additional calculations must be prepared, signed and sealed by the truss designer (a Florida-delegated engineer). Such additional drawings and calculations must be approved by the engineer or architect of record and must be submitted to the building official for review and approval.

2319.17.2.1.3

Roof trusses shall be designed for a minimum live load of 30 psf (1436 Pa), a minimum dead load of 15 psf (718 Pa) on the top chord, and a minimum dead load of 10 psf (479 Pa) on the bottom chord; and wind loads in accordance with Chapter 16 of this code. Where the roof design is such that water is not directed to the interior of the roof and there are no parapets or other roof edge drainage obstructions, roof trusses with slopes of 11/2:12 or greater may be designed for a live load of 20 psf (958 Pa) and a minimum total load of 45 psf (2155 Pa). Adjustment of the allowable design stress for load duration shall be in accordance with National Design Specification for Wood Construction.

2319.17.2.1.4

The allowable deflection under live load for trusses shall not exceed span/360 for plastered ceilings, span/240 for unplastered finished ceilings, or span/180 for trusses without a ceiling.

2319.17.2.1.5

Flat roof trusses shall be designed for not less than the loads set forth in Section 2319.17.2.1.3 above, except that the dead load on the top chord may be taken as 10 psf (479 Pa) in lieu of 15 psf (718 Pa), and the total load reduced to 50 psf (2394 Pa). Adjustment of the allowable design stress for load duration shall be in accordance with National Design Specification for Wood Construction.

2319.17.2.1.6

Where gable end trusses are permitted in this code, they shall be designed for a minimum live load of 30 psf (1436 Pa) and a minimum dead load of 15 psf (718 Pa) on the top chord. The minimum load of 10 psf (479 Pa) on the bottom chord may be omitted where continuous support is provided. In addition, the gable end trusses shall be designed to sustain wind load as specified in Chapter 16 (High-Velocity Hurricane Zones) but not less than 30 psf (1436 Pa) perpendicular to the plane of the truss. Such trusses shall use a rationally designed system to resist lateral wind loads and be anchored to the substructure at intervals no greater than 4 feet (1219 mm) on center to resist the uplift forces and shall be designed to transfer the loads to the substructure. The design of the system used to resist the lateral loads imposed on the truss shall be prepared by the engineer or architect of record.

2319.17.2.1.7

When girders exceed two members and when girder reactions exceed the capacity of standard connectors or hangers, these reactions shall be shown on the drawings and the connection must be designed, signed and sealed by a registered professional engineer or registered architect proficient in structural design and such design shall be included as part of the shop drawings.

2319.17.2.1.8

All trusses shall be properly braced to act as a system. Such bracing shall be included as part of the design document.

2319.17.2.2 Materials and Specifications

2319.17.2.2.1

Trusses shall be fabricated applying the design values listed in the standard Design Values for Wood Construction of the American Forest and Paper Association.

2319.17.2.2.2

Top and bottom chords shall be of No. 2 Grade or better. Web members shall be of No. 3 Grade or better. A chord member is defined as the entire top or bottom truss member which may consist of shorter spliced pieces.

2319.17.2.2.3

For trusses spanning 20 feet (6 m) or less, the minimum percentage of grade-marked members among top and bottom chords shall be 50 percent.

2319.17.2.2.4

For trusses spanning more than 20 feet (6 m) the minimum percentage of grade-marked members among top and bottom chords shall be 75 percent, and there shall be a minimum of one marked web on each truss.

2319.17.2.2.5

All lumber shall be 2 inches by 4 inches (51 mm by 102 mm) nominal or larger, and no 2-inch (51 mm) nominal member shall be less in size than 11/2 inches (38 mm).

2319.17.2.2.6

The moisture content of all lumber used in wood truss fabrication shall not exceed 19 percent.

2319.17.2.2.7

Connector plates shall be not less than 20 gauge galvanized steel meeting ASTM A653/A653M or A924/A924M, and shall be identified by the manufacturer's stamp. The size and location of all plates shall be shown on the truss design drawings. Connectors shall have product approval.

2319.17.2.2.8

All connector plates over 3 inches (76 mm) and 25 percent of 3 inches (76 mm) or less, as per TPI standards, shall bear the name, logo or other markings, which clearly identify the manufacturer. Semiannually, plate manufacturers shall certify compliance with the provisions of Section 6 of the Truss Plate Institute, TPI, National Design Standard for Metal Plate Connected Wood Truss Construction, with respect to the grade of steel, thickness or gauge of material, and galvanizing to ASTM G60 as a minimum. This certification requirement shall be satisfied by submitting by an approved independent laboratory to the certification agency.

2319.17.2.3 Fabrication

2319.17.2.3.1

Manufacturers of prefabricated wood truss assemblies shall obtain a valid certificate of competency from the authority having jurisdiction.

2319.17.2.3.2

Each truss shall bear the fabricators stamp on a web member and 75 percent shall be placed so as to be clearly visible after erection and before placement of ceiling.

2319.17.2.3.3

Multiple member girder trusses shall be predrilled at the truss plant for connection bolts only. Hanger bolt holes shall be drilled onsite, on a location indicated on approved drawings.

2319.17.2.3.4

Each manufacturer or fabricator shall retain the services of applicable organizations among those listed below for monthly inspections of the lumber grade used in fabrication. Following each inspection, a report shall be submitted by the inspection agency to the authority having jurisdiction. All inspection agencies providing any type of inspection services shall be approved by the authority having jurisdiction.

  • For Pine: Southern Pine Inspection Bureau or Timber Products grading agencies with appropriate jurisdiction.
  • For Douglas Fir, Hem-Fir or Fir-Larch: Western Wood Products Association or West Coast Lumber Inspection Bureau. Timber Products Inspection Inc., or other grading agencies with appropriate jurisdiction.

2319.17.2.3.5

In addition, the fabricator shall employ an approved testing laboratory to conduct inspections of fabrication compliance. Such inspections shall be made unannounced and at random at least once a month. Following each inspection, a report on approved forms shall be submitted by the laboratory to the authority having jurisdiction and such reports shall bear the date, signature and seal of the supervising Florida-registered architect or professional engineer.

2319.17.2.3.6

When there is evidence of noncompliance with the provisions for fabrication set forth in this paragraph or with the approved plans, the authority having jurisdiction may require the inspection laboratory to make additional job-site or plant inspections.

2319.17.2.3.7

The authority having jurisdiction may require load testing on noncomplying wood trusses. The test results shall be reported to the authority having jurisdiction.

2319.17.2.3.8

Failure of units tested or receipt of inspection reports indicating fabrication not in accordance with approved truss design drawings, or failure to submit required inspection and/or test reports, shall be cause for suspension or revocation of the certificate of competency of the manufacturer or fabricator.

2319.17.2.4 Truss Erection

2319.17.2.4.1

Reserved.

2319.17.2.4.2

Reserved.

2319.17.2.4.3

Reserved.

2319.17.2.4.4

At gable ends, this diaphragm shall be designed to transmit lateral loads imposed on the gable to roof diaphragms and/or ceiling diaphragms where available. Where the wall supporting the gable is not designed to withstand lateral loads independent of the gable (by using shear walls or other methods), anchorage of the gable to the wall shall be designed to transmit the loads from the wall to the bracing and the bracing designed to transmit the lateral loads from the gable and wall to the roof diaphragms and/or ceiling diaphragms where available. Ceiling diaphragms that provide lateral support at gable walls shall be designed by the architect or professional engineer of record, and shall have continuous bottom chord bracing, end restraints, intermediate restraints and conditions so as to sufficiently transfer the lateral loads at the top of the gable endwalls to the intersecting shear walls. In no case shall the rigid ceiling, as defined in Section 2319.17.1.2, be used as an integral part of the system needed for lateral bracing of the gable endwalls.

2319.17.2.4.5

Reserved.

Related Code Sections


2319.17.2 Wood, Prefabricated Wood Trusses
Prefabricated wood trusses shall comply with this section ...
2017 FBC - Building, 6th edition > 23 Wood > 2319 High-Velocity Hurricane Zones— Horizontal Framing > 2319.17 Wood Trusses > 2319.17.2 Prefabricated Wood Trusses
2319.17.2 Wood, Prefabricated Wood Trusses
Prefabricated wood trusses shall comply with this section ...
2014 FBC - Building, 5th edition > 23 Wood > 2319 High-Velocity Hurricane Zones— Horizontal Framing > 2319.17 Wood Trusses > 2319.17.2 Prefabricated Wood Trusses
2319.17.2 Wood, Prefabricated Wood Trusses
Prefabricated wood trusses shall comply with this section ...
2020 FBC - Building, 7th edition > 23 Wood > 2319 High-Velocity Hurricane Zones—Horizontal Framing > 2319.17 Wood Trusses > 2319.17.2 Prefabricated Wood Trusses
2319.17.2.4.2 Wood,
Reserved ...
2020 FBC - Building, 7th edition > 23 Wood > 2319 High-Velocity Hurricane Zones—Horizontal Framing > 2319.17 Wood Trusses > 2319.17.2 Prefabricated Wood Trusses > 2319.17.2.4 Truss Erection > 2319.17.2.4.2
2319.17.2.4.3 Wood,
Reserved ...
2017 FBC - Building, 6th edition > 23 Wood > 2319 High-Velocity Hurricane Zones— Horizontal Framing > 2319.17 Wood Trusses > 2319.17.2 Prefabricated Wood Trusses > 2319.17.2.4 Truss Erection > 2319.17.2.4.3
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE