R609.6.1 Preengineered Assemblies for Masonry Walls
Go To Full Code Chapter
R609.6.1.1
Unreinforced masonry units above an opening and 8-inch (203 mm) high bond beams above an opening shall be supported by an assembly.
R609.6.1.2
Preengineered assemblies shall be selected from a manufacturer's approved schedule or other approved tables for the load capacities based on the appropriate minimum gravity load carrying capacities established in Tables R609.6.1.2(1), R609.6.1.2(2), and R609.6.1.2(3).
Notes:
Notes:
Notes:

ROOF SPAN (FT) | UPLIFT (plf) | |||
GRAVITY (plf) | Vasd as determined in accordance with Section R301.2.1.3 | |||
100 mph | 120 mph | 140 mph | ||
42 | 150 | 85 | 112 | 165 |
12 | 330 | 152 | 204 | 305 |
24 | 600 | 262 | 351 | 525 |
36 | 870 | 374 | 502 | 745 |
44 | 1,050 | 451 | 605 | 900 |
52 | 1,230 | 530 | 710 | 1,055 |
60 | 1,410 | 609 | 816 | 1,215 |
- All loads are superimposed at the top of the wall and do not include dead loads of the bond beam or masonry above the assembly. Add 100 percent of additional dead loads to the gravity loads and subtract 85 percent of these loads from the uplift loads.
- Use 4-foot (1220 mm) roof span for assemblies in endwalls.
- For total roof dead loads over 10 psf, increase gravity loads by the following amount: (Roof Dead Load - 10 psf) × (Roof Span + 2 ft)/2.
- Uplift rating is required only if a pre-engineered assembly is used to directly support a roof. See Section R609.6.1.3 for cases where uplift need not be considered.

FLOOR SPAN1 (FT) | MINIMUM RATED GRAVITY LOAD ASSEMBLY (plf) | |||||
ASSEMBLY CLEAR SPAN (FT) | ||||||
4 | 6 | 8 | 12 | 16 | 20 | |
42 | 210 | 260 | 310 | 410 | 510 | 610 |
12 | 430 | 480 | 530 | 630 | 730 | 830 |
24 | 760 | 810 | 860 | 960 | 1,060 | 1,160 |
36 | 1,090 | 1,140 | 1,190 | 1,290 | 1,390 | 1,490 |
44 | 1,310 | 1,360 | 1,410 | 1,510 | 1,610 | 1,710 |
52 | 1,530 | 1,580 | 1,630 | 1,730 | 1,830 | 1,930 |
60 | 1,750 | 1,800 | 1,850 | 1,950 | 2,050 | 2,150 |
- For a wall supporting floors on both sides, enter table with the sum of the 2 full spans.
NOTE: Tabular values are for half the load of the full span shown. - Use 4-foot (1220 mm) building width for assemblies in walls not supporting floors (normally endwalls and interior masonry walls and shearwalls).
- The values in this table may be interpolated.
- These loads take into account the dead load of any masonry in the wall above the assembly and live and dead loads of the roof and floor supported. Dead load of the assembly is not included in the table and if not included in the preengineered concrete design must be added to the loads in the table.
- This table is applicable for all roof dead loads.
FLOOR SPAN1 (FT) | MINIMUM RATED GRAVITY LOAD ASSEMBLY (plf) | |||||
ASSEMBLY CLEAR SPAN (FT) | ||||||
4 | 6 | 8 | 12 | 16 | 20 | |
42 | 290 | 340 | 390 | 490 | 590 | 690 |
12 | 670 | 720 | 770 | 870 | 970 | 1,070 |
24 | 1,240 | 1,290 | 1,340 | 1,440 | 1,540 | 1,640 |
36 | 1,810 | 1,860 | 1,910 | 2,010 | 2,110 | 2,210 |
44 | 2,190 | 2,240 | 2,290 | 2,390 | 2,490 | 2,590 |
52 | 2,570 | 2,620 | 2,670 | 2,770 | 2,870 | 2,970 |
60 | 2,950 | 3,000 | 3,050 | 3,150 | 3,250 | 3,350 |
- For a wall supporting floors on both sides, enter table with the sum of the 2 full spans.
NOTE: Tabular values are for half the load of the full span shown. - Use 4-foot (1220 mm) building width for assemblies in nonfloor bearing walls (normally endwalls and interior masonry walls and shearwalls).
- The values in this table may be interpolated.
- These loads take into account the dead load of any masonry in the wall above the assembly and live and dead loads of the roof and floor supported. Dead load of the assembly is not included in the table and if not included in the preengineered concrete assembly design must be added to the loads in the table.
- This table is applicable for all roof dead loads.

R609.6.1.3
Preengineered assemblies may function as a bond beam over an opening provided that:
- The bond beam reinforcement is continuous through the assembly.
- The assembly has an uplift rating that equals or exceeds the appropriate value stipulated in Table R609.6.1.2(1) if the lintel directly supports a roof.
Exception:
If the reinforcement in the top of the assembly is equal to or greater than the reinforcement required in the bottom of the assembly by the manufacturer, uplift need not be considered.
R609.6.1.4
Preengineered assemblies spanning openings shall extend a minimum of 4 inches (102 mm) nominal past each side of the opening.
Upcodes Diagrams
Related Code Sections
R609.6.1 Wall Construction, Preengineered Assemblies for Masonry Walls
for assemblies in walls not supporting floors (normally endwalls and interior masonry walls and shearwalls).
The values in this table may be interpolated ...
R609.6 Wall Construction, Assemblies and Beams Spanning Openings
are utilized to form the bottom portion of the bond beam over the opening in masonry walls, the bottom reinforcement of the preengineered assemblies shall ...
R609.6.2 Wall Construction, Continuous Bond Beams Spanning Openings
preengineered assemblies are utilized to form the bottom portion of the bond beam over the opening in masonry walls, the bottom reinforcement ...
2223.8 Steel, Roof Sheets, Wall Sheets, Roof Panels and Wall Panels
Direct screw attached roof and wall sheets may be used as diaphragms ...
2223.8 Steel, Roof Sheets, Wall Sheets, Roof Panels and Wall Panels
and wall sheets may be used as diaphragms provided the sheets are a minimum of 24 gauge [0.0239 inch (0.6 mm) nominal] in thickness. Additionally ...