1224.34.6.3 Pre-Procedure/Recovery Accommodations
JUMP TO FULL CODE CHAPTER
If provided, pre-procedure/recovery patient care stations shall meet the following requirements:
- Pre-procedure and recovery area(s) shall be immediately accessible to procedure rooms and separate from corridors. The pre-procedure and recovery patient area or room shall be arranged to permit visual observation of the patient by staff before and after the procedure. Bays, cubicles, or single-bed rooms shall be permitted to serve as patient care stations.
- Area. Where open bays are used, each patient care station shall have a minimum clear floor area of 80 square feet (7.43 m2).
- Clearances. Each bay or cubicle shall have a minimum clearance of 3 feet (914 mm) between walls or partitions and the sides and foot of gurneys or patient beds. Each bay shall have a minimum clearance of 4 feet (1218 mm) between sides of gurneys or patient beds.
- Patient privacy. Provisions such as cubicle curtains shall be provided for patient privacy.
- Handwashing station. A handwashing station shall be provided within the pre-procedure/ recovery area.
Related Code Sections
1224.34.6.3 Interior Environment, Pre-Procedure/Recovery Accommodations
If provided, pre-procedure/recovery patient care stations shall meet the following requirements: Pre-procedure and recovery area(s) shall ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.34 Nuclear Medicine > 1224.34.6 Radiosurgery Suite > 1224.34.6.3 Pre-Procedure/Recovery Accommodations
1224.34.1.2 Interior Environment, Nuclear Medicine Room
materials are handled, prepared, or disposed of. Pre-procedure patient care and recovery area shall be provided to accommodate at least two stretchers ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.34 Nuclear Medicine > 1224.34.1 General > 1224.34.1.2 Nuclear Medicine Room
1224.28.4 Interior Environment, Interventional Imaging
Pre-procedure and recovery areas shall be immediately accessible to procedure rooms and separate from ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.28 Supplemental Surgery and Special Procedure Services > 1224.28.4 Interventional Imaging
1224.28 Interior Environment, Supplemental Surgery and Special Procedure Services
Pre-procedure and recovery areas shall be immediately accessible to procedure rooms and separate from corridors. The pre-procedure ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.28 Supplemental Surgery and Special Procedure Services
1224.34.1 Interior Environment, General
, or disposed of. Pre-procedure patient care and recovery area shall be provided to accommodate at least two stretchers. This area shall comply ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.34 Nuclear Medicine > 1224.34.1 General