Section 309 Powered Industrial Trucks and Equipment
JUMP TO FULL CODE CHAPTER
Powered industrial trucks and similar equipment including, but not limited to, floor scrubbers and floor buffers, shall be operated and maintained in accordance with Section 309.2 through 309.7.
Powered industrial trucks used in areas designated as hazardous (classified) locations in accordance with the California Electrical Code shall be listed and labeled for use in the environment intended in accordance with NFPA 505.
Battery chargers shall be of an approved type. Combustible storage shall be kept not less than 3 feet (915 mm) from battery chargers. Battery charging shall not be conducted in areas open to the public.
Ventilation shall be provided in an approved manner in battery-charging areas to prevent a dangerous accumulation of flammable gases.
Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger.
Powered industrial trucks using liquid fuel, LP-gas or hydrogen shall be refueled outside of buildings or in areas specifically approved for that purpose. Fixed fuel-dispensing equipment and associated fueling operations shall be in accordance with Chapter 23. Other fuel-dispensing equipment and operations, including cylinder exchange for LP-gas-fueled vehicles, shall be in accordance with Chapter 57 for flammable and combustible liquids or Chapter 61 for LP-gas.
Related Code Sections
Section 309 General Requirements, Powered Industrial Trucks and Equipment
Powered industrial trucks and similar equipment including, but not limited to, floor scrubbers and floor buffers, shall be operated and maintained ...
Section 309 General Requirements, Powered Industrial Trucks and Equipment
Powered industrial trucks and similar equipment including, but not limited to, floor scrubbers and floor buffers, shall be operated and maintained ...
309.3 General Requirements, Battery Chargers
Battery chargers shall be of an approved type. Combustible storage shall be kept not less than 3 feet (915 mm) from battery chargers. Battery charging ...
California Fire Code 2019 > 3 General Requirements > 309 Powered Industrial Trucks and Equipment > 309.3 Battery Chargers
309.4 General Requirements, Fire Extinguishers
Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 ...
California Fire Code 2016 > 3 General Requirements > 309 Powered Industrial Trucks and Equipment > 309.4 Fire Extinguishers
309.4 General Requirements, Ventilation
Ventilation shall be provided in an approved manner in battery-charging areas to prevent a dangerous accumulation of flammable gases ...