// CODE SNIPPET
7.2.1.9* Powered Door Leaf Operation
Go To Full Code Chapter
7.2.1.9.1* General
Where means of egress door leaves are operated by power upon the approach of a person or are provided with power-assisted manual operation, the design shall be such that, in the event of power failure, the leaves open manually to allow egress travel or close when necessary to safeguard the means of egress.
7.2.1.9.1.1
7.2.1.9.1.2
7.2.1.9.1.3
7.2.1.9.1.4
7.2.1.9.1.5
The door assembly shall be designed and installed so that, when a force is applied to the door leaf on the side from which egress is made, it shall be capable of swinging from any position to provide full use of the required width of the opening in which it is installed. (See 7.2.1.4.)
7.2.1.9.1.6
A readily visible, durable sign in letters not less than 1 in. (25 mm) high on a contrasting background that reads as follows shall be located on the egress side of each door opening:
IN EMERGENCY, PUSH TO OPEN
7.2.1.9.1.7
Sliding, power-operated door assemblies in an exit access serving an occupant load of fewer than 50 that manually open in the direction of door leaf travel, with forces not exceeding those required in 7.2.1.4.5, shall not be required to have the swing-out feature required by 7.2.1.9.1.5. The required sign shall be in letters not less than 1 in. (25 mm) high on a contrasting background and shall read as follows:
IN EMERGENCY, SLIDE TO OPEN
7.2.1.9.1.8*
In the emergency breakout mode, a door leaf located within a two-leaf opening shall be exempt from the minimum 32 in. (810 mm) single-leaf requirement of 7.2.1.2.3.2(1), provided that the clear width of the single leaf is not less than 30 in. (760 mm).
7.2.1.9.1.9
For a biparting sliding door assembly in the emergency breakout mode, a door leaf located within a multiple-leaf opening shall be exempt from the minimum 32 in. (810 mm) single-leaf requirement of 7.2.1.2.3.2(1) if a clear opening of not less than 32 in. (810 mm) is provided by all leafs broken out.
7.2.1.9.1.10
Door assemblies complying with 7.2.1.14 shall be permitted to be used.
7.2.1.9.1.11
The requirements of 7.2.1.9.1 through 7.2.1.9.1.10 shall not apply in detention and correctional occupancies where otherwise provided in Chapters 22 and 23.
7.2.1.9.2 Self-Closing or Self-Latching Door Leaf Operation
Where door leaves are required to be self-closing or self-latching and are operated by power upon the approach of a person, or are provided with power-assisted manual operation, they shall be permitted in the means of egress where they meet the following criteria:
- The door leaves can be opened manually in accordance with 7.2.1.9.1 to allow egress travel in the event of power failure.
- New door leaves remain in the closed position, unless actuated or opened manually.
- When actuated, new door leaves remain open for not more than 30 seconds.
- Door leaves held open for any period of time close — and the power-assist mechanism ceases to function — upon operation of approved smoke detectors installed in such a way as to detect smoke on either side of the door opening in accordance with the provisions of NFPA 72.
- Door leaves required to be self-latching are either self-latching or become self-latching upon operation of approved smoke detectors per 7.2.1.9.2(4).
- New power-assisted swinging door assemblies comply with BHMA/ANSI A156.19, Power Assist and Low Energy Power Operated Doors.
Related Code Sections
7.2.1.9* Means of Egress, Powered Door Leaf Operation
Where means of egress door leaves are operated by power upon the approach of a person or are provided with power-assisted manual operation ...
7.2.1.9.1.3 Means of Egress,
New low-energy power-operated sliding doors and low-energy power-operated folding doors shall comply with ANSI/BHMA A156.38, Low Energy Power ...
7.2.1.9.1.2 Means of Egress,
New power-assisted swinging doors and low-energy power-operated swinging doors shall comply with ANSI/BHMA A156.19, Power Assist and Low Energy Power ...
7.2.1.9.1.4 Means of Egress,
The forces required to manually open the door leaves specified in 7.2.1.9.1 shall not exceed those required in 7.2.1.4.5, except that the force ...
7.2.1.9.1.5 Means of Egress,
The door assembly shall be designed and installed so that, when a force is applied to the door leaf on the side from which egress is made, it shall ...