The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power systems. Secondary power shall be from an approved standby source complying with Chapter 27 of this code. The standby power source and its transfer switches shall be in a room separate from the normal power transformers and switch gears and ventilated directly to and from the exterior. The room shall be enclosed with not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The transfer to full standby power shall be automatic and within 60 seconds of failure of the primary power.
[F] 909.11.1 Power Sources and Power Surges
Elements of the smoke control system relying on volatile memories or the like shall be supplied with uninterruptable power sources of sufficient duration to span 15-minute primary power interruption. Elements of the smoke control system susceptible to power surges shall be suitably protected by conditioners, suppressors or other approved means.

Related Code Sections

513.11 Exhaust Systems, Power Systems
The smoke control system shall be supplied with two sources of power. Primary power shall be the normal building power systems. Secondary power shall ...
(D) Special Occupancies, Power Systems
Battery systems shall be installed in accordance with the requirements of Article 700, and generator systems shall be as described in 517.30 through ...
909.11 Fire Protection Systems, Power Systems
The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power systems. Secondary power ...
909.11 Fire Protection Systems, Power Systems
The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power systems. Secondary power ...
2703.15 Semiconductor Fabrication Facilities, Emergency Power System
An emergency power system shall be provided in Group H-5 occupancies in accordance with Section 1203. The emergency power system shall supply power ...