(E) Power Distribution Blocks
Go To Full Code Chapter
Power distribution blocks shall be permitted in pull and junction boxes over 1650 cm3 (100 in.3) for connections of conductors where installed in boxes and where the installation complies with 314.28(E)(1) through (E)(5).
(1) Installation
Power distribution blocks installed in boxes shall be listed.
(2) Size
In addition to the overall size requirement in the first sentence of 314.28(A)(2), the power distribution block shall be installed in a box with dimensions not smaller than specified in the installation instructions of the power distribution block.
(3) Wire Bending Space
(4) Live Parts
Power distribution blocks shall not have uninsulated live parts exposed within a box, whether or not the box cover is installed.
Related Code Sections
(E) Wiring Methods and Materials, Power Distribution Blocks
Power distribution blocks shall be permitted in pull and junction boxes over 1650 cm3 (100 in.3) for connections of conductors where installed ...
(E) Wiring Methods and Materials, Power Distribution Blocks
Power distribution blocks shall be permitted in pull and junction boxes over 1650 cm3 (100 in.3) for connections of conductors where installed ...
(B) Wiring Methods and Materials, Power Distribution Blocks
Power distribution blocks installed in metal wireways shall be listed. Power distribution blocks installed on the line side of the service equipment ...
(B) Wiring Methods and Materials, Power Distribution Blocks
Power distribution blocks installed in metal wireways shall be listed. Power distribution blocks installed on the line side of the service equipment ...
(2) Wiring Methods and Materials, Size of Enclosure
In addition to the wiring space requirement in 376.56(A), the power distribution block shall be installed in a wireway with dimensions not smaller ...