2.2-2.9.2.2 Postpartum Room
JUMP TO FULL CODE CHAPTER
- The postpartum room shall meet the requirements in Section 2.2-2.2.2 (Patient Room) with the exception of Section 2.2-2.22.2 (1) (Patient Room-Area).
- Space requirements. Patient rooms in the postpartum unit shall have a minimum clear floor area of 150 square feet (13.94 square meters) in single-patient rooms and 124 square feet (11.52 square meters) per bed in multiple-patient rooms.
Related Code Sections
2.2-2.9.2.2 Specific Requirements for General Hospitals, Postpartum Room
The postpartum room shall meet the requirements in Section 2.2-2.2.2 (Patient Room) with the exception of Section 2.2-2.22.2 (1) (Patient Room-Area ...
Guidelines for Design and Construction of Hospitals 2018 of Pennsylvania > 2.2 Specific Requirements for General Hospitals > 2.2-2 Patient Care Units > 2.2-2.9 Obstetrical Unit > *2.2-2.9.2 Antepartum and Postpartum Unit > 2.2-2.9.2.2 Postpartum Room
2.4-2.2.1.3 Specific Requirements for Birth Centers, Location
Birthing rooms shall be located to address privacy during occupancy for labor, birth, and postpartum care. Birthing rooms shall be located out ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.4 Specific Requirements for Birth Centers > *2.4-2 Birth Center Facilities > 2.4-2.2 Birthing Room > 2.4-2.2.1 General > 2.4-2.2.1.3 Location
2.4-2.2.1 Specific Requirements for Birth Centers, General
occupancy for labor, birth, and postpartum care. Birthing rooms shall be located out of the path of unrelated traffic and under direct supervision ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.4 Specific Requirements for Birth Centers > *2.4-2 Birth Center Facilities > 2.4-2.2 Birthing Room > 2.4-2.2.1 General
2.2-2.9.11.11 Specific Requirements for General Hospitals, Recovery Space for Cesarean Delivery Suite
) or labor-delivery-recovery-postpartum (LDRP) rooms are located in or directly accessible to the cesarean delivery suite, they shall be permitted ...
Guidelines for Design and Construction of Hospitals 2018 of Pennsylvania > 2.2 Specific Requirements for General Hospitals > 2.2-2 Patient Care Units > 2.2-2.9 Obstetrical Unit > 2.2-2.9.11 Cesarean Delivery Suite > 2.2-2.9.11.11 Recovery Space for Cesarean Delivery Suite
2.2-2.9 Specific Requirements for General Hospitals, Obstetrical Unit
-baby care unit for postpartum stay. Labor-Delivery-Recovery-Postpartum Model Single-room maternity care in labor ...
Guidelines for Design and Construction of Hospitals 2018 of Pennsylvania > 2.2 Specific Requirements for General Hospitals > 2.2-2 Patient Care Units > 2.2-2.9 Obstetrical Unit