• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

917.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2

NYC Building Code 2022 > 9 Fire Protection Systems > 917 Post-Fire Smoke Purge Systems > 917.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2
JUMP TO FULL CODE CHAPTER

917.2.1 General Design Requirements

Post-fire smoke purge systems are permitted to use dedicated equipment, the normal building HVAC system or other openings and shall have the capability to exhaust smoke from occupied spaces. Smoke removal may be by either mechanical or natural ventilation, but shall be capable of removing cold smoke. Smoke removed from a space must be discharged to a safe location outside the building and shall not be recirculated into the building in accordance with the New York City Mechanical Code.

917.2.2 Exhaust Capability

The system shall have an air supply and smoke exhaust capability that will provide a minimum of 6 air changes per hour or 1 cubic foot per minute per square foot (cfm/ft2) (0.00508 m3/s • m2), whichever is greater. The system need not exhaust from all areas at the same time, but is permitted to be zoned based on the largest fire area served. For the purpose of calculating system size, the height of a compartment shall be considered to run from slab to slab and include the volume above suspended ceilings. Provisions shall be made for sufficient make-up air. The provisions may include operable windows, doors, building leakage, or mechanical systems. In buildings having occupied floors located less than 75 feet (22 860 mm) above the lowest level of Fire Department vehicle access, breakable windows may be utilized.

917.2.3 Operation

The post-fire smoke purge system shall be operated by manual controls that are part of the fire command center, in accordance with Section 911, or fire alarm control unit when a fire command center is not required. Such control center or panel shall display a graphic indicating the portions of the building served by each post-fire smoke purge system. When a system is zoned into areas of operation less than the entire building, each zone shall have an individual control. Fire Department manual controls of post-fire smoke purge systems shall not override the manual or automatic operation of the smoke control system. Such Fire Department manual controls shall override the fire shutdown signal from the fire alarm system.

917.2.4 Interior Exit Stairways or Ramps or Exit Passageways in Occupancies Other Than Group R-2

Interior exit stairways or ramps or exit passageways shall not be used as a portion of the post-fire smoke purge system in occupancies other than Group R-2. Doors in interior exit stairways or ramps or exit passageways shall not be permitted to be used as a portion of the post-fire smoke purge system. Air transfer and duct openings associated with the post-fire smoke purge system shall not be permitted in the interior exit stairway or ramp or exit passageway.

Related Code Sections


917.2.4 Fire Protection Systems, Interior Exit Stairways or Ramps or Exit Passageways in Occupancies Other Than Group R-2
Interior exit stairways or ramps or exit passageways shall not be used as a portion of the post-fire smoke purge system in occupancies other than ...
NYC Building Code 2022 > 9 Fire Protection Systems > 917 Post-Fire Smoke Purge Systems > 917.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2 > 917.2.4 Interior Exit Stairways or Ramps or Exit Passageways in Occupancies Other Than Group R-2
912.2.3 Fire Protection Systems, Operation
of the building served by each post-fire smoke purge system. When a system is zoned into areas of operation less than the entire building, each zone shall have ...
NYC Building Code 2008 > 9 Fire Protection Systems > 912 Post-Fire Smoke Purge Systems > 912.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2 > 912.2.3 Operation
916.2.3 Fire Protection Systems, Operation
The post-fire smoke purge system shall be operated by manual controls that are part of the fire command center, in accordance with Section 911 ...
NYC Building Code 2014 > 9 Fire Protection Systems > 916 Post-Fire Smoke Purge Systems > 916.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2 > 916.2.3 Operation
916.2.2 Fire Protection Systems, Exhaust Capability
The system shall have an air supply and smoke exhaust capability that will provide a minimum of 6 air changes per hour or 1 cubic foot per minute per ...
NYC Building Code 2014 > 9 Fire Protection Systems > 916 Post-Fire Smoke Purge Systems > 916.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2 > 916.2.2 Exhaust Capability
917.2.2 Fire Protection Systems, Exhaust Capability
The system shall have an air supply and smoke exhaust capability that will provide a minimum of 6 air changes per hour or 1 cubic foot per minute per ...
NYC Building Code 2022 > 9 Fire Protection Systems > 917 Post-Fire Smoke Purge Systems > 917.2 Post-Fire Smoke Purge Systems in Occupancy Groups Other Than R-2 > 917.2.2 Exhaust Capability
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING