1112.2 Positive Displacement Compressor
JUMP TO FULL CODE CHAPTER
A positive
displacement compressor with a stop valve in the discharge
connection shall be equipped with a pressure-relief device
that is sized, and with a pressure setting, in accordance with
the compressor manufacturer to prevent rupture of the
compressor or to prevent the pressure from increasing to more
than 10 percent above the maximum allowable working pressure
of components located in the discharge line between the compressor and the stop valve or in accordance with Section
1113.5, whichever is larger. The pressure-relief device shall
discharge into the low-pressure side of the system or in accordance
with Section 1112.10.
Exception: Hermetic refrigerant motor-compressors that are listed and have a displacement not more than 50 cubic feet per minute (1.42 m3/min).
The relief device(s) shall be sized based on compressor flow at the following conditions:
Exception: Hermetic refrigerant motor-compressors that are listed and have a displacement not more than 50 cubic feet per minute (1.42 m3/min).
The relief device(s) shall be sized based on compressor flow at the following conditions:
- For compressors in single-stage systems and high-stage compressors of other systems, the flow shall be calculated based on 50°F (10°C) saturated suction temperature at the compressor suction.
- For low-stage or booster compressors in compound systems, the compressors that are capable of running only where discharging to the suction of a high-stage compressor, the flow shall be calculated based on the saturated suction temperature equal to the design operating intermediate temperature.
- For low-stage compressors in cascade systems, the compressors that are located in the lower-temperature stage(s) of cascade systems, the flow shall be calculated based on the suction pressure being equal to the pressure setpoint of the pressure-relieving devices that protect the lowside of the stage against overpressure.
- The compressor is equipped with capacity regulation.
- Capacity regulation actuates to a flow at not less than 90 percent of the pressure-relief device setting.
- A pressure-limiting device is installed and set in accordance with the requirements of Section 1111.0. [ASHRAE 15:9.8]
Related Code Sections
1112.2 Refrigeration, Positive Displacement Compressor
A positive
displacement compressor with a stop valve in the discharge
connection shall be equipped with a pressure-relief device
that is sized ...
Los Angeles Mechanical Code > 11 Refrigeration > 1112.0 Pressure-Relief Devices > 1112.2 Positive Displacement Compressor
1112.2 Refrigeration, Positive Displacement Compressor
A positive
displacement compressor with a stop valve in the discharge
connection shall be equipped with a pressure-relief device
that is sized ...
Los Angeles Mechanical Code > 11 Refrigeration > 1112.0 Pressure-Relief Devices > 1112.2 Positive Displacement Compressor
1111.2 Refrigeration, Setting
Pressure limiting devices shall be set in
accordance with one the following:
For positive displacement compressors:
When systems ...
1224.39.5.5.8 Interior Environment, Compressor Room
A compressor room shall be provided to house the chamber compressors, accumulator tanks and fire suppression system ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.39 Outpatient Service Space > 1224.39.5 Hyperbaric Therapy Service Space > 1224.39.5.5 Support Areas for the Hyperbaric Suite > 1224.39.5.5.8 Compressor Room
1226.5.14.5.8 Interior Environment, Compressor Room
Refer to Section 1224.39.5.5.8 ...
Los Angeles Building Code > 12 Interior Environment > 1226 [OSHPD 3] Clinics > 1226.5 Outpatient Clinical Services of a Hospital > 1226.5.14 Hyperbaric Therapy Service Space > 1226.5.14.5 Support Areas for the Hyperbaric Suite > 1226.5.14.5.8 Compressor Room