1106.5.1 Positioning of Aircraft Fuel-Servicing Vehicles
Go To Full Code Chapter
Aircraft-fueling vehicles shall not be located, parked or permitted to stand in a position where such unit would obstruct egress from an aircraft should a fire occur during fuel-transfer operations. Tank vehicles shall not be located, parked or permitted to stand under any portion of an aircraft.
1106.5.1.1 Fueling Vehicle Egress
A clear path shall be maintained for aircraft-fueling vehicles to provide for prompt and timely egress from the fueling area.
1106.5.1.2 Aircraft Vent Openings
A clear space of at least 10 feet (3048 mm) shall be maintained between aircraft fuel-system vent openings and any part or portion of an aircraft-fueling vehicle.
1106.5.1.3 Parking
Prior to leaving the cab, the aircraft-fueling vehicle operator shall ensure that the parking brake has been set. At least two chock blocks not less than 5 inches by 5 inches by 12 inches (127 mm by 127 mm by 305 mm) in size and dished to fit the contour of the tires shall be utilized and positioned in such a manner as to preclude movement of the vehicle in any direction.
Upcodes Diagrams
Related Code Sections
1106.5.1 Aviation Facilities, Positioning of Aircraft Fuel-Servicing Vehicles
Aircraft-fueling vehicles shall not be located, parked or permitted to stand in a position where such unit would obstruct egress from an aircraft ...
2006.5 Aviation Facilities, Fueling and Defueling
Aircraft-fueling vehicles shall not be located, parked or permitted to stand in a position ...
2006.5 Aviation Facilities, Fueling and Defueling
Aircraft-fueling vehicles shall not be located, parked or permitted to stand in a position ...
Section 1106 Aviation Facilities, Aircraft Fueling
to stand in a position where such unit would obstruct egress from an aircraft should a fire occur during fuel-transfer operations. Tank vehicles shall ...
1106.5 Aviation Facilities, Fueling and Defueling
Aircraft-fueling vehicles shall not be located, parked or permitted to stand in a position ...