// CODE SNIPPET
603.4.2 Portable Outdoor Gas-Fired Heating Appliances
JUMP TO FULL CODE CHAPTER
Portable gas-fired heating appliances located outdoors shall be in accordance with Sections 603.4.2.1 through 603.4.2.3.4.
Portable outdoor gas-fired heating appliances shall be located in accordance with Sections 603.4.2.1.1 through 603.4.2.1.4.
The storage or use of portable outdoor gas-fired heating appliances is prohibited in any of the following locations:
- Inside of any occupancy where connected to the fuel gas container.
- Inside of tents, canopies and membrane structures.
- On exterior balconies.Exception: As allowed in Section 6.22 of NFPA 58.
Portable outdoor gas-fired heating appliances shall be located not less than 5 feet (1524 mm) from buildings.
Portable outdoor gas-fired heating appliances shall not be located beneath, or closer than 5 feet (1524 mm) to combustible decorations and combustible overhangs, awnings, sunshades or similar combustible attachments to buildings.
Portable outdoor gas-fired heating appliances shall not be located within 5 feet (1524 mm) of exits or exit discharges.
Portable outdoor gas-fired heating appliances shall be installed and operated in accordance with Sections 603.4.2.2.1 through 603.4.2.2.4.
Portable outdoor gas-fired heating appliances shall be installed and maintained in accordance with the manufacturer's instructions.
Portable outdoor gas-fired heating appliances shall be equipped with a tilt or tip-over switch that automatically shuts off the flow of gas if the appliance is tilted more than 15 degrees (0.26 rad) from the vertical.
The heating element or combustion chamber of portable outdoor gas-fired heating appliances shall be permanently guarded so as to prevent accidental contact by persons or material.
Fuel gas containers for portable outdoor gas-fired heating appliances shall comply with Sections 603.4.2.3.1 through 603.4.2.3.4.
Only approved DOTn or ASME gas containers shall be used.
Replacement of fuel gas containers in portable outdoor gas-fired heating appliances shall not be conducted while the public is present.
The maximum individual capacity of gas containers used in connection with portable outdoor gas-fired heating appliances shall not exceed 20 pounds (9 kg).
Gas containers shall not be stored inside of buildings except in accordance with Section 6109.9.
Related Code Sections
605.5.2 Building Services and Systems, Portable Outdoor Gas-Fired Heating Appliances
Portable gas-fired heating appliances located outdoors shall be in accordance with Sections 605.5.2.1 through 605.5.2.3.4 ...
Fire Code 2021 of Colorado > 6 Building Services and Systems > 605 Fuel-Fired Appliances > 605.5 Portable Unvented Heaters > 605.5.2 Portable Outdoor Gas-Fired Heating Appliances
603.4.2 Building Services and Systems, Portable Outdoor Gas-Fired Heating Appliances
Portable gas-fired heating appliances located outdoors shall be in accordance with Sections 603.4.2.1 through 603.4.2.3.4 ...
Fire Code 2018 of Colorado > 6 Building Services and Systems > 603 Fuel-Fired Appliances > 603.4 Portable Unvented Heaters > 603.4.2 Portable Outdoor Gas-Fired Heating Appliances
605.5.2.1 Building Services and Systems, Location
Portable outdoor gas-fired heating appliances shall be used and located in accordance with Sections 605.5.2.1.1 through 605.5.2.1.4 ...
Fire Code 2021 of Colorado > 6 Building Services and Systems > 605 Fuel-Fired Appliances > 605.5 Portable Unvented Heaters > 605.5.2 Portable Outdoor Gas-Fired Heating Appliances > 605.5.2.1 Location
603.4.2.3 Building Services and Systems, Gas Containers
Fuel gas containers for portable outdoor gas-fired heating appliances shall comply with Sections 603.4.2.3.1 through 603.4.2.3.4 ...
Fire Code 2018 of Colorado > 6 Building Services and Systems > 603 Fuel-Fired Appliances > 603.4 Portable Unvented Heaters > 603.4.2 Portable Outdoor Gas-Fired Heating Appliances > 603.4.2.3 Gas Containers
605.5.2.3 Building Services and Systems, Gas Containers
Fuel gas containers for portable outdoor gas-fired heating appliances shall comply with Sections 605.5.2.3.1 through 605.5.2.3.4 ...
Fire Code 2021 of Colorado > 6 Building Services and Systems > 605 Fuel-Fired Appliances > 605.5 Portable Unvented Heaters > 605.5.2 Portable Outdoor Gas-Fired Heating Appliances > 605.5.2.3 Gas Containers