Portable space heaters fueled by piped natural gas shall be designed, operated and maintained in accordance with FC 313.6.1 through 313.6.5.
313.6.1 Clearance to Buildings
Heaters shall be located outdoors and at least 5 feet (1524 mm) from any building or structure.
313.6.2 Clearance to Combustible Materials
Heaters shall not be located beneath, or closer than 5 feet (1524 mm) to combustible decorations and combustible overhangs, awnings, sun control devices or similar combustible attachments to buildings or structures.
313.6.3 Proximity to Exits
Heaters shall not be located within 5 feet (1524 mm) of exits or exit discharges.
313.6.4 Tip-Over Switch
Heaters shall be equipped with a tilt or tip-over switch that automatically shuts off the flow of gas if the appliance is tilted more than 15 degrees (0.26 rad) from the vertical.
313.6.5 Guard Against Contact
The heating element or combustion chamber of heaters shall be permanently protected so as to prevent accidental contact by persons or material.
Upcodes Diagrams

Related Code Sections

303.3.1.4 General Regulations, Gas Piping
The appliance shall be installed with natural gas only. All gas piping shall be hard-piped with no flexible connectors. Pursuant to Section 27-2034(f ...
Section 630 Specific Appliances, Infrared Radiant Heaters
Infrared radiant heaters shall be tested in accordance with ANSI Z83.6 and shall be installed in accordance with the manufacturer's installation ...
Section 630 Specific Appliances, Infrared Radiant Heaters
heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall ...
§27-848.11 Heating and Combustion Equipment, Imitation Fireplaces
Only natural gas-fired fireplace heaters accepted in accordance with the provisions of article twelve of subchapter thirteen of this chapter shall ...
§27-886 Chimneys and Gas Vents, Special Venting Arrangements
appliances in lieu of natural draft vents. Where an exhauster is used with gas-burning equipment requiring venting, provisions shall be made ...