2404.6.1.2.2 Portable Infrared Apparatus
JUMP TO FULL CODE CHAPTER
When a portable infrared drying apparatus is used, electrical wiring and portable infrared drying equipment shall comply with NFPA 70. Electrical equipment located within 18 inches (457 mm) of floor level shall be approved for Class I, Division 2 hazardous locations. Metallic parts of drying apparatus shall be electrically bonded and grounded. During spraying operations, portable drying apparatus and electrical connections and wiring thereto shall not be located within spray booths, spray rooms or other areas where spray residue would be deposited thereon.
Related Code Sections
2404.6.1.2.2 Flammable Finishes, Portable Infrared Apparatus
Where a portable infrared drying apparatus is used, electrical wiring and portable infrared drying equipment shall comply with NFPA 70. Electrical ...
2020 Minnesota State Fire Code > 24 Flammable Finishes > 2404 Spray Finishing > 2404.6 Sources of Ignition > 2404.6.1 Drying Operations > 2404.6.1.2 Drying Apparatus > 2404.6.1.2.2 Portable Infrared Apparatus
2404.6.1.2.2 Flammable Finishes, Portable Infrared Apparatus
When a portable infrared drying apparatus is used, electrical wiring and portable infrared drying equipment shall comply with NFPA 70. Electrical ...
Minnesota Fire Code 2015 > 24 Flammable Finishes > 2404 Spray Finishing > 2404.6 Sources of Ignition > 2404.6.1 Drying Operations > 2404.6.1.2 Drying Apparatus > 2404.6.1.2.2 Portable Infrared Apparatus
2404.6 Flammable Finishes, Sources of Ignition
apparatus is used, electrical wiring and portable infrared drying equipment shall comply with NFPA 70. Electrical equipment located within 18 inches (457 ...
2020 Minnesota State Fire Code > 24 Flammable Finishes > 2404 Spray Finishing > 2404.6 Sources of Ignition
(D) Special Occupancies, Portable Equipment
] Exception No. 2: Where portable electric drying apparatus is used in spray booths and the following requirements are met: The apparatus and its ...
National Electrical Code, 2020 > 5 Special Occupancies > 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials > 516.6 Wiring and Equipment in Class I Locations > (D) Portable Equipment