// CODE SNIPPET
604.10 Portable, Electric Space Heaters
JUMP TO FULL CODE CHAPTER
Only listed and labeled portable, electric space heaters shall be used.
Portable, electric space heaters shall be plugged directly into an approved receptacle.
Portable, electric space heaters shall not be plugged into extension cords.
Portable, electric space heaters shall not be operated within 3 feet (914 mm) of any combustible materials. Portable, electric space heaters shall be operated only in locations for which they are listed.
Where used in Group I-2 and ambulatory care facilities, portable, electric space heaters shall be limited to those having a heating element that cannot exceed a temperature of 212°F (100°C), and such heaters shall only be used in nonsleeping staff and employee areas.
Related Code Sections
604.10 Building Services and Systems, Portable, Electric Space Heaters
Where not prohibited by other sections of this code, portable, electric space heaters shall be permitted to be used in all occupancies in accordance ...
California Fire Code 2019 > 6 Building Services and Systems > 604 Electrical Equipment, Wiring and Hazards > 604.10 Portable, Electric Space Heaters
605.10 Building Services and Systems, Portable, Electric Space Heaters
Where not prohibited by other sections of this code, portable, electric space heaters shall be permitted to be used in all occupancies other than ...
California Fire Code 2016 > 6 Building Services and Systems > 605 Electrical Equipment, Wiring and Hazards > 605.10 Portable, Electric Space Heaters
604.10.2 Building Services and Systems, Power Supply
Portable, electric space heaters shall be plugged directly into an approved receptacle ...
California Fire Code 2019 > 6 Building Services and Systems > 604 Electrical Equipment, Wiring and Hazards > 604.10 Portable, Electric Space Heaters > 604.10.2 Power Supply
605.10.1 Building Services and Systems, Listed and Labeled
Only listed and labeled portable, electric space heaters shall be used ...
California Fire Code 2016 > 6 Building Services and Systems > 605 Electrical Equipment, Wiring and Hazards > 605.10 Portable, Electric Space Heaters > 605.10.1 Listed and Labeled
605.10.2 Building Services and Systems, Power Supply
Portable, electric space heaters shall be plugged directly into an approved receptacle ...
California Fire Code 2016 > 6 Building Services and Systems > 605 Electrical Equipment, Wiring and Hazards > 605.10 Portable, Electric Space Heaters > 605.10.2 Power Supply