Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

1910.306(k)(4) Portable Distribution and Termination Boxes

OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes
JUMP TO FULL CODE CHAPTER
Employers may only use portable distribution and termination boxes that meet the following requirements:

1910.306(k)(4)(i)

Boxes shall be designed so that no live parts are exposed to accidental contact. Where installed outdoors, the box shall be of weatherproof construction and mounted so that the bottom of the enclosure is not less than 152 mm (6 in.) above the ground;

1910.306(k)(4)(iii)

Receptacles shall have overcurrent protection installed within the box. The overcurrent protection may not exceed the ampere rating of the receptacle, except as permitted in ยง 1910.305(j)(4) for motor loads;

1910.306(k)(4)(iv)

Where single-pole connectors are used, they shall comply with the following:

1910.306(k)(4)(iv)(A)

Where ac single-pole portable cable connectors are used, they shall be listed and of the locking type. Where paralleled sets of current-carrying single-pole separable connectors are provided as input devices, they shall be prominently labeled with a warning indicating the presence of internal parallel connections. The use of single-pole separable connectors shall comply with at least one of the following conditions:

1910.306(k)(4)(iv)(A)(1)

Connection and disconnection of connectors are only possible where the supply connectors are interlocked to the source and it is not possible to connect or disconnect connectors when the supply is energized; or

1910.306(k)(4)(iv)(A)(2)

Line connectors are of the listed sequential-interlocking type so that load connectors are connected in the following sequence:

1910.306(k)(4)(iv)(A)(2)(i)

Equipment grounding conductor connection;

1910.306(k)(4)(iv)(A)(2)(iii)

Ungrounded conductor connection; and so that disconnection is in the reverse order; or

1910.306(k)(4)(iv)(A)(2)(ii)

Grounded circuit-conductor connection, if provided; and

1910.306(k)(4)(iv)(A)(3)

A caution notice is provided adjacent to the line connectors indicating that plug connection must be in the following sequence:

1910.306(k)(4)(iv)(A)(3)(i)

Equipment grounding conductor connection;

1910.306(k)(4)(iv)(A)(3)(iii)

Ungrounded conductor connection; and indicating that disconnection is in the reverse order; and

1910.306(k)(4)(iv)(A)(3)(ii)

Grounded circuit-conductor connection, if provided; and

1910.306(k)(4)(iv)(B)

Single-pole separable connectors used in portable professional motion picture and television equipment may be interchangeable for ac or dc use or for different current ratings on the same premises only if they are listed for ac/dc use and marked to identify the system to which they are connected;

1910.306(k)(4)(v)

Overcurrent protection of equipment and conductors shall be provided; and

1910.306(k)(4)(vi)

The following equipment connected to the same source shall be bonded:

1910.306(k)(4)(vi)(A)

Metal raceways and metal sheathed cable;

1910.306(k)(4)(vi)(B)

Metal enclosures of electrical equipment; and

1910.306(k)(4)(vi)(C)

Metal frames and metal parts of rides, concessions, trailers, trucks, or other equipment that contain or support electrical equipment.

1910.306(k)(4)(ii)

Busbars shall have an ampere rating not less than the overcurrent device supplying the feeder supplying the box. Busbar connectors shall be provided where conductors terminate directly on busbars;

Related Code Sections


1910.306(k)(4) Electrical, Portable Distribution and Termination Boxes
Employers may only use portable distribution and termination boxes that meet the following requirements ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes
1910.306(k)(4)(iv)(A) Electrical,
Where ac single-pole portable cable connectors are used, they shall be listed and of the locking type. Where paralleled sets of current-carrying ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A)
1910.306(k)(4)(iv)(A)(1) Electrical,
Connection and disconnection of connectors are only possible where the supply connectors are interlocked to the source and it is not possible ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A) > 1910.306(k)(4)(iv)(A)(1)
1910.306(k)(4)(iv)(A)(2) Electrical,
Line connectors are of the listed sequential-interlocking type so that load connectors are connected in the following sequence ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A) > 1910.306(k)(4)(iv)(A)(2)
1910.306(k)(4)(iv)(A)(2)(i) Electrical,
Equipment grounding conductor connection ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A) > 1910.306(k)(4)(iv)(A)(2) > 1910.306(k)(4)(iv)(A)(2)(i)
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING