1910.306(k)(4) Portable Distribution and Termination Boxes
JUMP TO FULL CODE CHAPTER
Employers may only use portable distribution and termination boxes that meet the following requirements:
Boxes shall be designed so that no live parts are exposed to accidental contact. Where installed outdoors, the box shall be of weatherproof construction and mounted so that the bottom of the enclosure is not less than 152 mm (6 in.) above the ground;
Receptacles shall have overcurrent protection installed within the box. The overcurrent protection may not exceed the ampere rating of the receptacle, except as permitted in ยง 1910.305(j)(4) for motor loads;
Where single-pole connectors are used, they shall comply with the following:
Where ac single-pole portable cable connectors are used, they shall be listed and of the locking type. Where paralleled sets of current-carrying single-pole separable connectors are provided as input devices, they shall be prominently labeled with a warning indicating the presence of internal parallel connections. The use of single-pole separable connectors shall comply with at least one of the following conditions:
Connection and disconnection of connectors are only possible where the supply connectors are interlocked to the source and it is not possible to connect or disconnect connectors when the supply is energized; or
Line connectors are of the listed sequential-interlocking type so that load connectors are connected in the following sequence:
Equipment grounding conductor connection;
Ungrounded conductor connection; and so that disconnection is in the reverse order; or
Grounded circuit-conductor connection, if provided; and
A caution notice is provided adjacent to the line connectors indicating that plug connection must be in the following sequence:
Equipment grounding conductor connection;
Ungrounded conductor connection; and indicating that disconnection is in the reverse order; and
Grounded circuit-conductor connection, if provided; and
Single-pole separable connectors used in portable professional motion picture and television equipment may be interchangeable for ac or dc use or for different current ratings on the same premises only if they are listed for ac/dc use and marked to identify the system to which they are connected;
Overcurrent protection of equipment and conductors shall be provided; and
The following equipment connected to the same source shall be bonded:
Metal raceways and metal sheathed cable;
Metal enclosures of electrical equipment; and
Metal frames and metal parts of rides, concessions, trailers, trucks, or other equipment that contain or support electrical equipment.
Busbars shall have an ampere rating not less than the overcurrent device supplying the feeder supplying the box. Busbar connectors shall be provided where conductors terminate directly on busbars;
Related Code Sections
1910.306(k)(4) Electrical, Portable Distribution and Termination Boxes
Employers may only use portable distribution and termination boxes that meet the following requirements ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes
1910.306(k)(4)(iv)(A) Electrical,
Where ac single-pole portable cable connectors are used, they shall be listed and of the locking type. Where paralleled sets of current-carrying ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A)
1910.306(k)(4)(iv)(A)(1) Electrical,
Connection and disconnection of connectors are only possible where the supply connectors are interlocked to the source and it is not possible ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A) > 1910.306(k)(4)(iv)(A)(1)
1910.306(k)(4)(iv)(A)(2) Electrical,
Line connectors are of the listed sequential-interlocking type so that load connectors are connected in the following sequence ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A) > 1910.306(k)(4)(iv)(A)(2)
1910.306(k)(4)(iv)(A)(2)(i) Electrical,
Equipment grounding conductor connection ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(k) Carnivals, Circuses, Fairs, and Similar Events > 1910.306(k)(4) Portable Distribution and Termination Boxes > 1910.306(k)(4)(iv) > 1910.306(k)(4)(iv)(A) > 1910.306(k)(4)(iv)(A)(2) > 1910.306(k)(4)(iv)(A)(2)(i)