UpCodes logo
Go To Full Code Chapter
Portable containers used for cryogenic fluids located outdoors shall be separated from exposure hazards in accordance with Table 63.4.6.3. [55:8.6.3]

Table 63.4.6.3 Minimum Separation Distance Between  Portable Cryogenic Containers and Exposures
 
Minimum Distance
Exposure
ft
m
(1) Building exits 
10
3.1
(2) Wall openings
 1
0.3
(3) Air intakes 
10
3.1
(4) Property lines
5
1.5
(5) Room or area exits
3
 0.9
(6) Combustible materials, (e.g., paper, leaves, weeds, dry grass, or debris) 
15
4.5
(7) Incompatible hazardous materials
 20
6.1
[55: Table 8.6.3]
63.4.6.3.1
Non-bulk portable containers of liquefied hydrogen shall be separated from exposure hazards in accordance with Table 63.4.6.3.1. [55:8.6.3.1]


Table 63.4.6.3.1 Distance to Exposures for Non-Bulk Liquefied Hydrogen (LH2)
 
Minimum Distance to Buildings on the Same Property
Maximum Amount per Storage Area (gal)
Minimum Distance Between Storage Areas (ft)
Minimum Distance to Lot Lines of Property That Can Be Built Upon (ft)
Minimum Distance to Public Streets, Public Alleys, or Public Ways (ft)
Less than 2-Hour Construction
2-Hour Construction
4-Hour Construction
0-39.7
5
5
5
5
0
0
39.8-186.9
10
10
10
10
5
0
187-448.7
10
15
15
20
5
0
448.8-747.8
10
20
20
20
5
0
>747.8
20
25
25
20
5
0
For SI units: 1 ft = 305 mm.
Notes:
  1. For requirements on minimum distance to air intakes, see 63.3.6.2.4.
  2. For requirements on minimum distance to building openings including exits, see 63.3.6.2.5.
  3. When 63.4.6.3.2 is used as a means of distance reduction, the configuration of the fire barriers should be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations.
[55:Table 8.6.3.1]
63.4.6.3.2 Fire Barriers
A 2-hour fire barrier wall shall be permitted in lieu of the distances specified by Table 63.4.6.3 or Table 63.4.6.3.1 when in accordance with the provisions of 63.4.6.3.2.1 through 63.4.6.3.2.4. [55:8.6.3.2]
63.4.6.3.2.1
The fire barrier wall shall be without openings or penetrations. [55:8.6.3.2.1]
63.4.6.3.2.1.1
Penetrations of the fire barrier wall by conduit or piping shall be permitted provided that the penetration is protected with a firestop system in accordance with the building code. [55:8.6.3.2.1.1]
63.4.6.3.2.2
The fire barrier wall shall be either an independent structure or the exterior wall of the building adjacent to the storage system. [55:8.6.3.2.2]
63.4.6.3.2.3
The fire barrier wall shall be located not less than 5 ft (1.5 m) from any exposure. [55:8.6.3.2.3]
63.4.6.3.2.4
The fire barrier wall shall not have more than two sides at approximately 90 degree (1.57 rad) directions or not more than three sides with connecting angles of approximately 135 degrees (2.36 rad). [55:8.6.3.2.4]
Upcodes Diagrams

Related Code Sections

63.4.4.1.1 Compressed Gases and Cryogenic Fluids, Portable Containers
Portable cryogenic containers shall be marked in accordance with CGA C-7, Guide to the Preparation of Precautionary Labeling and Marking ...
63.4.4.1.1.1 Compressed Gases and Cryogenic Fluids,
Portable cryogenic containers shall be marked in accordance with CGA C-7, Guide to the Preparation of Precautionary Labeling and Marking ...
63.4.4.1.1.1 Compressed Gases and Cryogenic Fluids,
Portable cryogenic containers shall be marked in accordance with CGA C-7, Guide to the Preparation of Precautionary Labeling and Marking ...