1211.12 Polyvinyl Chloride (PVC) Pipe
Go To Full Code Chapter
Joints between polyvinyl chloride pipe or fittings shall be installed in accordance with one of the following methods:
- Mechanical joints shall be designed to provide a permanent seal and shall be of the mechanical or push-on joint. The mechanical joint shall include a pipe spigot that has a wall thickness to withstand without deformation or collapse; the compressive force exerted where the fitting is tightened. The push-on joint shall have a minimum wall thickness of the bell at any point between the ring and the pipe barrel. The elastomeric gasket shall comply with ASTM D3139, and be of such size and shape as to provide a compressive force against the spigot and socket after assembly to provide a positive seal.
- Solvent cement joints for PVC pipe or fittings shall be clean from dirt and moisture. Pipe shall be cut square and pipe shall be deburred. Where surfaces to be joined are cleaned and free of dirt, moisture, oil, and other foreign material, apply primer purple in color in accordance with ASTM F656. Primer shall be applied until the surface of the pipe and fitting is softened. Solvent cements in accordance with ASTM D2564 shall be applied to all joint surfaces. Joints shall be made while both the inside socket surface and outside surface of pipe are wet with solvent cement. Hold joint in place and undisturbed for 1 minute after assembly.
- Threads shall comply with ASME B1.20.1. A minimum of Schedule 80 shall be permitted to be threaded; however, the pressure rating shall be reduced by 50 percent. The use of molded fittings shall not result in a 50 percent reduction in the pressure rating of the pipe provided that the molded fittings shall be fabricated so that the wall thickness of the material is maintained at the threads. Thread sealant compound that is compatible with the pipe and fitting, insoluble in water, and nontoxic shall be applied to male threads. Caution shall be used during assembly to prevent over tightening of the PVC components once the thread sealant has been applied. Female PVC threaded fittings shall be used with plastic male threads only.
Related Code Sections
1211.12 Hydronics, Polyvinyl Chloride (PVC) Pipe
Joints between polyvinyl chloride pipe or fittings shall be installed in accordance with one of the following methods:
Mechanical joints shall ...
P3009.14.10 Sanitary Drainage, Distribution Piping
(PE) plastic pipe ASTM F 405 Polyvinyl chloride (PVC) plastic pipe ASTM D 2729 Polyvinyl chloride (PVC) plastic pipe with a 3.5-inch O.D ...
P3009.11 Sanitary Drainage, Distribution Piping
) plastic pipe ASTM F405 Polyvinyl chloride (PVC) plastic pipe ASTM D2729 Polyvinyl chloride (PVC) plastic pipe with a 3.5-inch O.D. and solid ...
P3002.1 Sanitary Drainage, Piping Within Buildings
pipe ASTM A53 Polyolefin pipe CSA B181.3 Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including schedule 40, DR 22 (PS 200) and DR ...
P3002.1 Sanitary Drainage, Piping Within Buildings
B 306
Galvanized steel pipe
ASTM A 53
Polyolefin pipe
CSA B181.3
Polyvinyl chloride (PVC) plastic pipe in IPS diameters ...