1203.10 Polybutylene Plastic Pipe and Tubing
JUMP TO FULL CODE CHAPTER
Joints between polybutylene plastic pipe and tubing or fittings shall be mechanical joints conforming to Section 1203.3 or heat-fusion joints conforming to Section 1203.10.1.
Joints shall be of the socket-fusion or butt-fusion type. Joint surfaces shall be clean and free of moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM D 3309.
Related Code Sections
1203.10 Hydronic Piping, Polybutylene Plastic Pipe and Tubing
Joints between polybutylene plastic pipe and tubing or fittings shall be mechanical joints conforming to Section 1203.3 or heat-fusion joints ...
2017 FBC - Mechanical, 6th edition > 12 Hydronic Piping > 1203 Joints and Connections > 1203.10 Polybutylene Plastic Pipe and Tubing
1203.10 Hydronic Piping, Polybutylene Plastic Pipe and Tubing
Joints between polybutylene plastic pipe and tubing or fittings shall be mechanical joints conforming to Section 1203.3 or heat-fusion joints ...
2014 FBC - Mechanical, 5th edition > 12 Hydronic Piping > 1203 Joints and Connections > 1203.10 Polybutylene Plastic Pipe and Tubing
1203.10 Hydronic Piping, Polybutylene Plastic Pipe and Tubing
Joints between polybutylene plastic pipe and tubing or fittings shall be mechanical joints conforming to Section 1203.3 or heatfusion joints ...
2020 FBC - Mechanical, 7th edition > 12 Hydronic Piping > 1203 Joints and Connections > 1203.10 Polybutylene Plastic Pipe and Tubing
1209.1 Hydronic Piping, Materials
Piping for heating panels shall be standard-weight steel pipe, Type L copper tubing, polybutylene or other approved plastic pipe or tubing rated ...
1209.1 Hydronic Piping, Materials
Piping for heating panels shall be standard-weight steel pipe, Type L copper tubing, polybutylene or other approved plastic pipe or tubing rated ...