454.1.9.2.1.4 Plunge Pool Main Drains
JUMP TO FULL CODE CHAPTER
The plunge pool shall have a minimum of one main drain with separate piping and valve to the filtration system collector tank. The velocity through the openings of the main drain grate shall not exceed 11/2 feet per second (457 mm/s) at the design flow rate of the recirculation pump. The main drain piping shall be sized to handle 100 percent of the design flow rate of the filtration system with a maximum flow velocity of 3 feet (914 mm) per second.
Related Code Sections
454.1.9.2.1.4 Special Detailed Requirements Based on Use and Occupancy, Plunge Pool Main Drains
The plunge pool shall have a minimum of one main drain with separate piping and valve to the filtration system collector tank. The velocity through ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.2 Water Slides > 454.1.9.2.1 Water Slide Plunge Pool > 454.1.9.2.1.4 Plunge Pool Main Drains
454.1.9.2.1.4 Special Detailed Requirements Based on Use and Occupancy, Plunge Pool Main Drains
The plunge pool shall have a minimum of one main drain with separate piping and valve to the filtration system collector tank. The velocity through ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.2 Water Slides > 454.1.9.2.1 Water Slide Plunge Pool > 454.1.9.2.1.4 Plunge Pool Main Drains
454.1.9.2.1.4 Special Detailed Requirements Based on Occupancy and Use, Plunge Pool Main Drains
The plunge pool shall have a minimum of one main drain with separate piping and valve to the filtration system collector tank. The velocity through ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.2 Water Slides > 454.1.9.2.1 Water Slide Plunge Pool > 454.1.9.2.1.4 Plunge Pool Main Drains
454.1.9.2.3.6 Special Detailed Requirements Based on Use and Occupancy,
The pump reservoir shall be fed by main drains within the plunge pool itself (either in the floor or side wall). They shall have the maximum flow ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.2 Water Slides > 454.1.9.2.3 Pump Reservoirs > 454.1.9.2.3.6
454.1.9.2.3.6 Special Detailed Requirements Based on Use and Occupancy,
The pump reservoir shall be fed by main drains within the plunge pool itself (either in the floor or side wall). They shall have the maximum flow ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.2 Water Slides > 454.1.9.2.3 Pump Reservoirs > 454.1.9.2.3.6