1705.12.6 Plumbing, Mechanical and Electrical Components

Building Code 2015 of Utah > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.12 Special Inspections for Seismic Resistance > 1705.12.6 Plumbing, Mechanical and Electrical Components
JUMP TO FULL CODE CHAPTER
Periodic special inspection of plumbing, mechanical and electrical components shall be required for the following:

1. Anchorage of electrical equipment for emergency and standby power systems in structures assigned to Seismic Design Category C, D, E or F.

2. Anchorage of other electrical equipment in structures assigned to Seismic Design Category E or F.

3. Installation and anchorage of piping systems designed to carry hazardous materials and their associated mechanical units in structures assigned to Seismic Design Category C, D, E or F.

4. Installation and anchorage of ductwork designed to carry hazardous materials in structures assigned to Seismic Design Category C, D, E or F.

5. Installation and anchorage of vibration isolation systems in structures assigned to Seismic Design Category C, D, E or F where the approved construction documents require a nominal clearance of 1/4 inch (6.4 mm) or less between the equipment support frame and restraint.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1705.12.6 Special Inspections and Tests, Plumbing, Mechanical and Electrical Components
Periodic special inspection of plumbing, mechanical and electrical components shall be required for the following: 1. Anchorage of electrical ...
Building Code 2015 of Utah > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.12 Special Inspections for Seismic Resistance > 1705.12.6 Plumbing, Mechanical and Electrical Components
1705.12.6 Special Inspections and Tests, Plumbing, mechanical and electrical components
Periodic special inspection of plumbing, mechanical and electrical components shall be required for the following: Anchorage of electrical ...
Building Code 2018 of Utah > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.12 Special inspections for seismic resistance > 1705.12.6 Plumbing, mechanical and electrical components
1402.7 Exterior Walls, Flood resistance for coastal high-hazard areas and coastal A zones
For buildings in coastal high-hazard areas and coastal A zones as established in Section 1612.3, electrical, mechanical and plumbing system ...
Building Code 2018 of Utah > 14 Exterior Walls > 1402 Performance Requirements > 1402.7 Flood resistance for coastal high-hazard areas and coastal A zones
1403.7 Exterior Walls, Flood Resistance for Coastal High-Hazard Areas and Coastal a Zones
For buildings in coastal high-hazard areas and coastal A zones as established in Section 1612.3, electrical, mechanical and plumbing system ...
Building Code 2015 of Utah > 14 Exterior Walls > 1403 Performance Requirements > 1403.7 Flood Resistance for Coastal High-Hazard Areas and Coastal a Zones
R322.1.6 Building Planning, Protection of Mechanical, Plumbing and Electrical Systems
Electrical systems, equipment and components; heating, ventilating, air conditioning; plumbing appliances and plumbing fixtures; duct systems ...
Residential Code 2015 of Utah > 3 Building Planning > R322 Flood-Resistant Construction > R322.1 General > R322.1.6 Protection of Mechanical, Plumbing and Electrical Systems
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US