3315.2 Platforms
Go To Full Code Chapter
3315.2.1 Planking
Platforms shall have a floor consisting of at least 2-inch (51 mm) planking spanning
as permitted by Table 3314.5.2. Planking shall be laid close and shall be butt-joined and securely
fastened.
Exceptions:
- Where the platform is to be used to support loads in excess of 75 psf (366.2 kg/m2), or is intended for a use as specified in rules promulgated by the commissioner, the platform shall be designed by a registered design professional.
- Where the platform is to be used by motorized equipment, including but not limited to trucks, power buggies, fork lifts, or scissor lifts, the platform shall be designed by a registered design professional.
3315.2.2 Guardrail Required
A guardrail meeting the requirements of Sections
3308.7.1 through 3308.7.7 shall be provided in any of the following circumstances:
- Where an unprotected side or edge is 6 feet (1829 mm) or more above the ground, floor, or other lower level;
- Along any portion of the runway or ramp that abuts motor vehicle traffic; or
- Along any portion of the runway or ramp where a person may thereby be exposed to harm from adjoining machinery, electrical equipment, or other hazardous equipment.
3315.2.3 Netting Required
Where it is possible for the public to pass under, or next to,
platforms, the space between the top rail and the toeboard shall be enclosed with a wire screen comprised of not less than number 18 gauge wire mesh, or
equivalent synthetic netting that is flame retardant in accordance with NFPA 701, with
openings in the wire or synthetic mesh no larger than 1/2 inch (13 mm) in the vertical or horizontal
dimensions and 3/4 inch (19 mm) in any other dimension.
Upcodes Diagrams
Related Code Sections
3314.15.7 Safeguards During Construction or Demolition, Platforms
The platforms of every two-point adjustable suspended scaffold shall be ladder-type, plank-type, beam-type, light-metal type, or another type ...
3314.15.7 Safeguards During Construction or Demolition, Platforms
The platforms of every two-point suspension scaffold shall be ladder-type, plank-type, beam-type, light-metal type, or another type acceptable ...
3314.15.7 Safeguards During Construction or Demolition, Platforms
The platforms of every two-point adjustable suspended scaffold shall be ladder-type, plank-type, beam-type, light-metal type, or another type ...
3315.2 Safeguards During Construction or Demolition, Platforms
Platforms shall comply with the requirements of Sections 3315.2.1 through 3315.2.3 ...
3315.2 Safeguards During Construction or Demolition, Platforms
Platforms shall comply with the requirements of Sections 3315.2.1 through 3315.2.3 ...