403.6 Plastic Pipe, Tubing and Fittings
JUMP TO FULL CODE CHAPTER
Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to ASTM D2513. Such pipe shall be marked "Gas" and "ASTM D2513."
Plastic pipe, tubing and fittings, other than polyethylene, shall be identified and conform to the 2008 edition of ASTM D2513. Such pipe shall be marked "Gas" and "ASTM D2513."
Polyvinyl chloride (PVC) and chlorinated polyvinyl chloride (CPVC) plastic pipe, tubing and fittings shall not be used to supply fuel gas.
Plastic pipe, tubing and anodeless risers shall comply with the following:
- Factory-assembled anodeless risers shall be recommended by the manufacturer for the gas used and shall be leak tested by the manufacturer in accordance with written procedures.
- Service head adapters and field-assembled anodeless risers incorporating service head adapters shall be recommended by the manufacturer for the gas used, and shall be designed and certified to meet the requirements of Category I of ASTM D2513, and U.S. Department of Transportation, Code of Federal Regulations, Title 49, Part 192.281(e). The manufacturer shall provide the user with qualified installation instructions as prescribed by the U.S. Department of Transportation, Code of Federal Regulations, Title 49, Part 192.283(b).
The use of plastic pipe, tubing and fittings in undiluted liquefied petroleum gas piping systems shall be in accordance with NFPA 58.
Plastic pipe and fittings used to connect regulator vents to remote vent terminations shall be PVC conforming to ANSI/UL 651. PVC vent piping shall not be installed indoors.
Related Code Sections
403.6 Gas Piping Installations, Plastic Pipe, Tubing and Fittings
Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to the 2009 edition of ASTM D 2513. Such pipe shall be marked ...
2014 FBC - Fuel Gas, 5th edition > 4 Gas Piping Installations > 403 (IFGS) Piping Materials > 403.6 Plastic Pipe, Tubing and Fittings
403.6 Gas Piping Installations, Plastic Pipe, Tubing and Fittings
Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to ASTM D2513. Such pipe shall be marked "Gas" and "ASTM D2513 ...
2020 FBC - Fuel Gas, 7th edition > 4 Gas Piping Installations > 403 (IFGS) Piping Materials > 403.6 Plastic Pipe, Tubing and Fittings
403.6 Gas Piping Installations, Plastic Pipe, Tubing and Fittings
Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to ASTM D2513. Such pipe shall be marked "Gas" and "ASTM D2513 ...
2017 FBC - Fuel Gas, 6th edition > 4 Gas Piping Installations > 403 (IFGS) Piping Materials > 403.6 Plastic Pipe, Tubing and Fittings
G2414.6 Fuel Gas, (403.6) Plastic Pipe, Tubing and Fittings
Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to ASTM D2513. Such pipe shall be marked "Gas" and "ASTM D2513 ...
2017 FBC - Residential, 6th edition > 24 Fuel Gas > G2414 (403) Piping Materials > G2414.6 (403.6) Plastic Pipe, Tubing and Fittings
G2414.6 Fuel Gas, (403.6) Plastic Pipe, Tubing and Fittings
Polyethylene plastic pipe, tubing and fittings used to supply fuel gas shall conform to ASTM D2513. Such pipe shall be marked "Gas" and "ASTM D2513 ...
2020 FBC - Residential, 7th edition > 24 Fuel Gas > G2414 (403) Piping Materials > G2414.6 (403.6) Plastic Pipe, Tubing and Fittings