5104.1.1 Plastic Level 1 Aerosol Products
Go To Full Code Chapter
Aerosol products in plastic containers larger than 4 fluid ounces (118 ml), but not to exceed 33.8 fluid ounces (1000 ml), shall be allowed only where in accordance with this section. The commodity classification shall be Class III commodities, as defined in NFPA 13 where any of the following conditions are met:
- Base product does not have a fire point where tested in accordance with ASTM D92, and nonflammable propellant.
- Base product does not sustain combustion as tested in accordance with Appendix H, "Method of Testing for Sustained Combustibility," in DOTn 49 CFR Part 173, and nonflammable propellant.
- Base product contains up to 20 percent by volume (15.8 percent by weight) of ethanol, isopropyl alcohol or a combination thereof in an aqueous mix, and nonflammable propellant.
- Base product contains 4 percent by weight or less of an emulsified flammable liquefied gas propellant within an aqueous base. The propellant shall remain emulsified for the life of the product. Where such propellant is not permanently emulsified, the propellant shall be nonflammable.
Related Code Sections
5104.1.1 Aerosols, Plastic Level 1 Aerosol Products
Aerosol products in plastic containers larger than 4 fluid ounces (118 ml), but not to exceed 33.8 fluid ounces (1000 ml), shall be allowed only ...
Section 5103 Aerosols, Classification of Aerosol Products
Aerosol products shall be classified as Level 1, 2 or 3 in accordance with Table 5103.1 and NFPA 30B. Aerosol products in cartons ...
Section 2802 Aerosols, Definitions
of their chemical heats of combustion and shall be designated Level 1, Level 2 or Level 3. Level 1 aerosol products. Those with a total chemical heat ...
Section 5104 Aerosols, Inside Storage of Aerosol Products
The inside storage of Level 2 and 3 aerosol products shall comply with Sections 5104.2 through 5104.8 and NFPA 30B. Level 1 aerosol products ...
5103.1 Aerosols, Classification Levels
Aerosol products shall be classified as Level 1, 2 or 3 in accordance with Table 5103.1 and NFPA 30B. Aerosol products in cartons ...