704.1.2.3.6 Piping Outdoors
JUMP TO FULL CODE CHAPTER
Piping installed above ground, outdoors, shall be securely supported and located where it will be protected from physical damage. Piping passing through an exterior wall of a building shall be encased in a protective pipe sleeve. The annular space between the piping and the sleeve shall be sealed from the inside such that the sleeve is ventilated to the outdoors. Where passing through an exterior wall of a building, the piping shall also be protected against corrosion by coating or wrapping with an inert material. Below-ground piping shall be protected against corrosion.
Related Code Sections
704.1.2.3.6 Gaseous Hydrogen Systems, Piping Outdoors
Piping installed above ground, outdoors, shall be securely supported and located where it will be protected from physical damage. Piping passing ...
Fuel Gas Code 2009 of Alabama > 7 Gaseous Hydrogen Systems > 704 (IFGC) Piping, Use and Handling > 704.1 Applicability > 704.1.2 Piping Systems > 704.1.2.3 Piping Design and Construction > 704.1.2.3.6 Piping Outdoors
704.1.2.3.6 Gaseous Hydrogen Systems, Piping Outdoors
Piping installed above ground, outdoors, shall be securely supported and located where it will be protected from physical damage. Piping passing ...
Fuel Gas Code 2015 of Alabama > 7 Gaseous Hydrogen Systems > 704 (IFGC) Piping, Use and Handling > 704.1 Applicability > 704.1.2 Piping Systems > 704.1.2.3 Piping Design and Construction > 704.1.2.3.6 Piping Outdoors
G2415.9 Fuel Gas, (404.9) Above-Ground Piping Outdoors
Piping installed outdoors shall be elevated not less than 3 1 / 2 inches (152 mm) above ground and where installed across roof surfaces, shall ...
Residential Code 2015 of Alabama > 24 Fuel Gas > G2415 (404) Piping System Installation > G2415.9 (404.9) Above-Ground Piping Outdoors
404.7 Gas Piping Installations, Above-Ground Outdoor Piping
All piping installed outdoors shall be elevated not less than 3 1 / 2 inches (152 mm) above ground and where installed across roof surfaces, shall ...
Fuel Gas Code 2009 of Alabama > 4 Gas Piping Installations > 404 (IFGC) Piping System Installation > 404.7 Above-Ground Outdoor Piping
404.9 Gas Piping Installations, Above-Ground Outdoor Piping
Piping installed outdoors shall be elevated not less than 3 1 / 2 inches (89 mm) above ground and where installed across roof surfaces, shall ...
Fuel Gas Code 2015 of Alabama > 4 Gas Piping Installations > 404 (IFGC) Piping System Installation > 404.9 Above-Ground Outdoor Piping