Ground-source heat-pump ground-loop pipe and tubing shall conform to the standards listed in Table M2105.4.
TABLE M2105.4
GROUND-SOURCE LOOP PIPE
MATERIAL STANDARD
Chlorinated polyvinyl chloride (CPVC) ASTM D2846; ASTM F437; ASTM F438; ASTM F439;
ASTM F441; ASTM F442; CSA B137.6
Cross-linked polyethylene (PEX) ASTM F876; CSA B137.5; ANSI/CSA/IGSHPA C448; NSF 358-3
High-density polyethylene (HDPE) ASTM D2737; ASTM D3035; ASTM F714;
AWWA C901; CSA B137.1; ANSI/CSA/IGSHPA C448; NSF 358-1
Polyethylene/aluminum/polyethylene (PE-AL-PE) pressure pipe ASTM F1282; AWWA C903; CSA B137.9
Polypropylene (PP-R) ASTM F2389; CSA B137.11; NSF 358-2
Polyvinyl chloride (PVC) ASTM D1785; ASTM D2241; CSA B137.3
Raised temperature polyethylene (PE-RT) ASTM F2623; ASTM F2769; CSA B137.18;
ANSI/CSA/IGSHPA C448; NSF 358-4
Upcodes Diagrams

Related Code Sections

M2105.4 Hydronic Piping, Piping and Tubing Materials Standards
Ground-source heat-pump ground-loop pipe and tubing shall conform to the standards listed in Table M2105.4. TABLE M2105.4 GROUND-SOURCE LOOP ...
1210.4 Hydronic Piping, Piping and Tubing Materials Standards
Ground-source heat pump ground-loop pipe and tubing shall conform to the standards listed in Table 1210.4. TABLE 1210.4 GROUND-SOURCE LOOP PIPE ...
1210.4 Hydronic Piping, Piping and Tubing Materials Standards
Ground-source heat pump ground-loop pipe and tubing shall conform to the standards listed in Table 1210.4. TABLE 1210.4 GROUND-SOURCE LOOP PIPE ...
1210.4 Hydronic Piping, Piping and Tubing Materials Standards
Ground-source heat pump ground-loop pipe and tubing shall conform to the standards listed in Table 1210.4. TABLE 1210.4 GROUND-SOURCE LOOP ...
7.3.1 Requirements for System Components and Hardware, General
Pipe or tube shall meet or exceed one of the standards in Table 7.3.1.1 or be in accordance with 7.3.3. Table 7.3.1.1 Pipe or Tube Materials ...